manualshive.com logo in svg
background image

 

 

 

Manual 

WAGO PERSPECTO

®

 762 

 

 

 

762-3057/000-001  

CP 57 QVGA TV 

PERSPECTO

®

 CP, Control Panel with CoDeSys 

Target Visualization 

Version 1.2.1  

 

 

 

Содержание WAGO-PERSPECTO 762 Series

Страница 1: ...Manual WAGO PERSPECTO 762 762 3057 000 001 CP 57 QVGA TV PERSPECTO CP Control Panel with CoDeSys Target Visualization Version 1 2 1 ...

Страница 2: ...2 WAGO PERSPECTO 762 762 3057 000 001 CP 57 QVGA TV Manual Version 1 2 1 2018 WAGO Kontakttechnik GmbH Co KG All rights reserved ...

Страница 3: ...rget Visualization PERSPECTO CP TV 13 3 2 View 14 3 2 1 Front View 14 3 2 2 Back View 15 3 3 Connectors 16 3 3 1 X1 Supply Voltage 16 3 3 2 X2 Serial Interfaces RS 232 COM 3 and RS 485 RS 422 COM 2 17 3 3 3 X3 Serial Interface RS 232 COM 1 18 3 3 4 X5 CAN 0 Interface 19 3 3 5 X6 ETHERNET Interface 20 3 3 6 X8 X9 USB Interfaces 21 3 4 Battery Case 22 3 5 Slot for Memory Card 23 3 6 Operating Elemen...

Страница 4: ...Address 33 6 3 The WAGO Control Center 34 6 3 1 Starting the WAGO Control Center 34 6 3 2 General Tab 35 6 3 3 Autostart Applications Tab 36 6 3 4 Users Tab 37 6 3 5 FTP Tab 38 6 3 6 HTTP Tab 39 6 3 7 RAS Tab 40 6 3 8 Backup Restore Tab 41 6 3 9 Advanced Tab 43 6 3 10 Saving the Configuration 44 6 4 Target Visu 45 6 5 Note Task Priority 45 7 Service 46 7 1 Battery Maintenance 46 List of Figures 47...

Страница 5: ...subsequent user In addition ensure that any supplement to this documentation is included if necessary 1 1 Scope of Validity This documentation applies to PERSPECTO Panel 762 3057 000 001 CP 57 QVGA TV 1 2 Copyright This Manual including all figures and illustrations is copyright protected Any further use of this Manual by third parties that violate pertinent copyright provisions is prohibited Repr...

Страница 6: ...s a moderate risk potentially hazardous situation which if not avoided could result in death or serious injury Personal Injury Indicates a low risk potentially hazardous situation which if not avoided may result in minor or moderate injury Damage to Property Indicates a potentially hazardous situation which if not avoided may result in damage to property Damage to Property Caused by Electrostatic ...

Страница 7: ...O 762 Notes about this Documentation 7 762 3057 000 001 CP 57 QVGA TV Manual Version 1 2 1 Additional Information Refers to additional information which is not an integral part of this documentation e g the Internet ...

Страница 8: ...iles are marked in italic type e g C Program Files WAGO Software Menu Menu items are marked in bold letters e g Save A greater than sign between two names means the selection of a menu item from a menu e g File New Input Designation of input or optional fields are marked in bold letters e g Start of measurement range Value Input or selective values are marked in inverted commas e g Enter the value...

Страница 9: ... electrical specialists with sufficient knowledge in automation technology These specialists must be familiar with the current standards and guidelines for the devices and the automated environments All changes to the controller shall always be performed by qualified personnel with sufficient skills in PLC programming 2 1 3 Use of the 762 Series in Compliance with Underlying Provisions 762 Series ...

Страница 10: ...the hardware or software that are not described in the operating instructions Improper use of the components Further details are given in the contractual agreements Please send your request for modified and new hardware or software configurations directly to WAGO Kontakttechnik GmbH Co KG Pixel error in TFT display Any pixel errors of the TFT display due to production reasons do not represent grou...

Страница 11: ...thorized staff only by means of specific keys or tools Replace defective or damaged devices Replace defective or damaged device module e g in the event of deformed contacts since the long term functionality of device module involved can no longer be ensured Protect the components against materials having seeping and insulating properties The components are not resistant to materials having seeping...

Страница 12: ... devices equipped with ETHERNET or RJ 45 connectors in LANs Never connect these devices with telecommunication networks Avoid electrostatic discharge The devices are equipped with electronic components that may be destroyed by electrostatic discharge when touched Please observe the safety precautions against electrostatic discharge per DIN EN 61340 5 1 3 When handling the devices please ensure tha...

Страница 13: ...nels and controllers 3 1 Control Panel with Target Visualization PERSPECTO CP TV In addition to target visualization the control panel with target visualization also has a CODESYS runtime making it a full fledged automation device PERSPECTO CP provides configurable functions for operation and monitoring and can independently process control tasks The PLC functionality is based on the IEC 61131 com...

Страница 14: ...cription WAGO PERSPECTO 762 762 3057 000 001 CP 57 QVGA TV Manual Version 1 2 1 3 2 View 3 2 1 Front View Figure 1 Front View Table 3 Legend for Figure Front View No Description 1 Front panel 2 Touch screen display ...

Страница 15: ...Housing 2 X1 Connection for 24VDC power supply 3 X2 RS 232 serial interface COM 3 or RS 485 RS 422 serial interfaces COM 2 as D sub 9 connector 4 X3 RS 232 serial interface as D sub 9 connector 5 X5 CAN Bus 0 CANopen interface as RJ45 jack 6 X8 X9 USB host interfaces 7 X6 ETHERNET interface as RJ45 jack 8 Service Service button 9 3V Battery CR1 2AA Battery case 10 X13 Slot for SD memory card ...

Страница 16: ...oltage Use the X1 connection for the device power supply More information about the power supply and power consumption is available in the Technical Data section Figure 3 Connector X1 Supply Voltage Table 5 X1 Pin Assignment Pin Assignment Function 1 24 V Supply Voltage 2 0 V GND Reference potential GND 3 FE Ground conductor ...

Страница 17: ...ce They are generally used for communication service devices modem operation etc Both interfaces may be operated together The connected data cable must be shielded Figure 4 Connector X2 Serial Interfaces RS 232 and RS 485 RS422 Table 6 X2 Pin Assignment Pin Assignment Function 1 Y Tx RS 485 RS 422 2 RxD Receive Data for RS 232 3 TxD Transmit Data for RS 232 4 Z Tx RS 485 RS 422 5 GND 5V Signal Gro...

Страница 18: ...s The connected data cable must be shielded A null modem connection is used to connect to another device with RS 232 interface A 1 1 connecting cable is used to connect to a modem Figure 5 Connector X3 Serial Interface RS 232 Table 7 X3 Pin Assignment Pin Assignment Function 1 DCD Data carrier detect 2 RxD Receive Data for RS 232 3 TxD Transmit Data for RS 232 4 DTR Data Terminal ready 5 GND 5V Si...

Страница 19: ...igned with electrical isolation in accordance with ISO 11898 A terminating resistor that can be switched on by relay is integrated in the device in accordance with ISO11898 The connected data cable must be shielded Figure 6 Connector X5 CAN 0 Interface RJ 45 Table 8 X5 Pin Assignment Pin Assignment Function 1 CAN_L CAN data low dominant 2 CAN H CAN data high dominant 3 GND Ground 4 Not used 5 Do n...

Страница 20: ...guidelines for ETHERNET interfaces If there are more than 2 devices in a network then they must be connected to each other by a HUB or SWITCH A 1 1 cable is used here If there are only 2 devices in a network a crossover cable can be used Figure 7 Connector X6 ETHERNET RJ45 Table 9 X6 Pin Assignment Pin Assignment Function 1 TX Transmit Data 2 TX Transmit Data 3 RX Receive Data 4 n c 5 n c 6 RX Rec...

Страница 21: ...t interfaces type A The following table and illustration provide information on the pin assignment of the interfaces The interface connection meets the USB specification 2 0 Figure 8 Connectors X8 X9 USB Interfaces Table 10 X8 X9 Pin Assignment Pin Assignment Function 1 USB_VCC1 USB 5V DC 2 USB_N1 USB data line N1 3 USB_P1 USB data line P1 4 USB_GND USB GND ...

Страница 22: ...t holds a 3 V lithium battery type CR1 2AA or Z3600A that supplies the real time clock and the SRAM with power in case of a power failure If you want to change the lithium battery during a power failure make sure that you have the new battery ready to hand For a certain time a gold cap capacitor provides the required power The data of the volatile memory SRAM is therefore preserved during a batter...

Страница 23: ...CP 57 QVGA TV Manual Version 1 2 1 3 5 Slot for Memory Card The panel 762 3057 000 001 is equipped with a Flash memory slot on the side for an SD card It supports cards with a 2 GB maximum Supported memory cards item no 758 879 000 001 are available from WAGO ...

Страница 24: ...57 QVGA TV Manual Version 1 2 1 3 6 Operating Elements 3 6 1 Service Button The service switch on the back of the device is used to call up the Windows CD desktop The WAGO Control Center can be launched for example to configure the device Figure 10 Service Button ...

Страница 25: ...e of protection Front IP65 back IP20 3 7 2 Power Supply Table 12 Technical Data Power Supply Voltage supply DC 24 V 18 V 30 V Max input current 24 V 250 mA Operating power 8 W 12 W Buffer battery CR 1 2 AA 3 7 3 Display Table 13 Technical Data Display Display type TFT Screen size diagonal 14 5 cm 5 7 Display colors 262 000 colors Graphics resolution 320 x 240 pixels Contrast ratio 500 1 Angle of v...

Страница 26: ...ng system Windows CE 6 0 Software configuration PLC runtime with target visualization CODESYS panel configuration software 3 7 6 Interfaces Table 16 Technical Data Interfaces USB interfaces 2 x USB2 0 host type A ETHERNET interface 1 x 10 100 Mbit RJ 45 CAN interface 1 x CANopen RJ 45 Serial interfaces 1 x RS 232 D sub 9 1 x RS 232 RS 485 D sub 9 Maximum length of connecting cables USB maximum 3 m...

Страница 27: ...n granted to 762 3057 000 001 panels LR Lloyd s Register Env 1 2 3 4 RINA Registro Italiano Navale 3 9 Standards and Guidelines 762 3057 000 001 panels meet the following requirements on emission and immunity of interference EMC CE Immunity to interference EN 61000 6 2 EMC CE Emission of interference EN 61000 6 4 EMC marine applications Immunity to interference acc to DNV GL EMC marine application...

Страница 28: ...osition If the panel is mounted in a position different than recommended cooling can be affected Contact WAGO Service for more information The PERSPECTO Series panels are used in the panel cutout provided and bolted down with the included clamping elements and the intermediate plate from behind note the following installation diagram Do no forget the intermediate plate Insert the included intermed...

Страница 29: ...nting 29 762 3057 000 001 CP 57 QVGA TV Manual Version 1 2 1 Figure 12 Detailed Photograph of Installation with Intermediate Plate Information on the dimensions of the panel cutout is available in the Technical Data section ...

Страница 30: ...s The interfaces to the back of the device are used to connect the peripheral devices electrically The number and arrangement of the interfaces depend on the design note the information in the Technical Data chapter or Connection chapter The RS 232 interface is used to program and diagnose the devices Various software tools can be used for modem operation remote maintenance etc The RS 485 RS 422 i...

Страница 31: ...panels from launching automatically the touch screen must be touched within a adjustable time period default setting 3 s after the boot self test phase The service switch on the back of the device can be used to launch the Windows CE desktop at any time The WAGO Control Center can be used to change the start behavior of the device Time window for launching the Windows CE desktop The WAGO Control C...

Страница 32: ...w its IP address from a DHCP server on the network or the device can be assigned a fixed IP address The current IP address can be queried by double clicking on the network icon in the system tray in the task bar DHCP fixed IP address The device must be connected to a network to change the IP address from DHCP to a fixed IP address 6 2 2 Setting the IP Address The WAGO Control Center is used to set...

Страница 33: ...a crossover cable to connect between the panel and configuring PC directly it is recommended that both devices have fixed IP addresses with an open address in the range 192 168 1 xxx In this case the subnet mask is automatically set to 255 255 255 0 There is no default gateway IP Address The devices must be set to different IP addresses ...

Страница 34: ...gure the device Settings for the Autostart programs uses FTP HTTP and RAS access can be made General device settings can also be checked and modified 6 3 1 Starting the WAGO Control Center The WAGO Control Center is launched from the Start menu Start Programs Utilities WAGO Control Center The tabs of the WAGO Control Center are explained on the following pages ...

Страница 35: ...al Watchdog A watchdog can be configured here which can restart the device if it crashes after a set time Don t start Windows CE Shell If the checkbox is enabled the Windows CE desktop can no longer be launched The task bar is no longer displayed Simple Network Time protocol If there is an Internet connection the system clock of the device can be synchronized via an SNTP server Client Only If the ...

Страница 36: ...u can enter programs here that should launch automatically after booting The target visu runtime the autoscan function and the WAGO Control Center are entered here by default The time window for launching the programs after the boot and self test phase of the device can also be set here Figure 15 Autostart Applications Tab ...

Страница 37: ...tected tree for example can be put in the user s home directory By doing so you gain access to this and subsequent directories FTP Home Directory HTTP directory path The user starts downwards from this menu The use cannot get to higher level directories Rights Access rights assigned to users are displayed here Access Rights If no home directory is set for a user the user gets FULL ACCESS to the pa...

Страница 38: ...ERSPECTO 762 762 3057 000 001 CP 57 QVGA TV Manual Version 1 2 1 6 3 5 FTP Tab You can configure the FTP server of the device here More information about creating users is available in the Users Tab section Figure 17 FTP Tab ...

Страница 39: ... configure the Web server of the device here Figure 18 HTTP Tab Application example An httptest directory with the test alias was created on the flash disk A Web page index htm was created in this directory The page can be used in a Web browser to access the following address http IP address of the device test ...

Страница 40: ... is a service for remote access to a Windows CE device Figure 19 RAS Tab Both RAS functions server and client are supported The connection between a RAS client and the RAS server can be established via a modem VPM or direct connection For more information about the Remote Access Service RAS of the device please contact WAGO Support ...

Страница 41: ... Stick wago backup registry reg HKEY_LOCAL_MACHINE Drivers BuiltIn BackLight MaxIntensity The section devices the registry entries to be saved The path indicates where the registry entries shall be saved The registry entries to be saved are listed there SRAM Destination path filename or automatically sram bin Memory Stick wago backup sram The path indicates where the SRAM content shall be saved FI...

Страница 42: ... the backup_restore cfg and entries on the target data carrier The Restore button is used to restore the parameters defined in the backup_restore cfg and entries on the device Create backup It is recommended that you create a backup after commissioning the device and to keep the backup in a safe place Operating system update There is no operating system update for the device ...

Страница 43: ...explanatory Figure 21 Advanced Tab Restrictions for Control Panels with CoDeSys Target Visualization Control Panels with Target Visualization have no contrast and touch beeper setting Communication CAN bus termination Select this checkbox to switch on the CAN bus termination resistor of the CAN 0 interface COM Port Selection of X2 interface usage not possible for CP35 TV and CP57 TV ...

Страница 44: ... the Configuration After configuring the panel the settings must be permanently saved in the registry Call up the following utility program Start Programs Utilities Save Registry Fail safe saving of the configuration If the settings are not saved as described they are lost when the device is restarted ...

Страница 45: ... Status Window This window displays the loaded CODESYS programs with project details The CODESYS program can also be started or reset from here The Shutdown button can be used to exit the runtime 6 5 Note Task Priority Task Priority When creating a CODESYS project both VISU_TASK with priority 21 and VISU_INPUT_TASK with priority 20 are created If possible these priorities should not be modified ...

Страница 46: ...sk of fire or explosion Data loss If the device is switched off when the battery has failed or has reached its capacity without replacing the battery any settings not saved are lost The battery in the device control buffers the adjustable parameters and the time for a power failure or switched off device Replace the battery as follows 1 Make sure that the device has been on for at least 10 minutes...

Страница 47: ...ace RJ 45 19 Figure 7 Connector X6 ETHERNET RJ45 20 Figure 8 Connectors X8 X9 USB Interfaces 21 Figure 9 Battery Case 22 Figure 10 Service Button 24 Figure 11 Installation of the Clamping Elements 28 Figure 12 Detailed Photograph of Installation with Intermediate Plate 29 Figure 13 IP Address 33 Figure 14 General Tab 35 Figure 15 Autostart Applications Tab 36 Figure 16 Users Tab 37 Figure 17 FTP T...

Страница 48: ...Figure Back View 15 Table 5 X1 Pin Assignment 16 Table 6 X2 Pin Assignment 17 Table 7 X3 Pin Assignment 18 Table 8 X5 Pin Assignment 19 Table 9 X6 Pin Assignment 20 Table 10 X8 X9 Pin Assignment 21 Table 11 Technical Data Housing 25 Table 12 Technical Data Power Supply 25 Table 13 Technical Data Display 25 Table 14 Technical Data Hardware 26 Table 15 Technical Data Software 26 Table 16 Technical D...

Страница 49: ...WAGO PERSPECTO 762 49 762 3057 000 001 CP 57 QVGA TV Manual Version 1 2 1 ...

Страница 50: ......

Отзывы: