765-4501/0100-0000
Functions
Product manual | Version: 1.1.0
49
8PORT IOL-A FLD EI DC 24V 2.0A
5.4 Overload Protection
The module has internal overload protection for the output current. The output currently is
constantly measured and monitored for values exceeding the maximum.
If the measured output current exceeds the maximum value, the product reduces the cur-
rent or switches the corresponding loads off.
5.5 Parameterization Tools
5.5.1 Overview
There are several ways to set the product’s parameters. The following table provides an
overview of the tools.
Table 38: Overview of Parameterization Tools
Tool
Description
Controller with EtherNet/IP
scanner
The
EtherNet/IP scanner
must be configured to exchange process data with the
modules. The EDS file
wago_0765450x.eds
(x = 1 ... 4) describes a WAGO I/O
System Field module. The configuration of the EtherNet/IP scanner can import this
EDS file.
The user can configure and parameterize a module. The user loads the configura-
tion onto the EtherNet/IP scanner. The EtherNet/IP scanner configures the module
via EtherNet/IP. Whether or not the scanner sends parameters (the port configura-
tion) depends on the connection selected.
For example, if connection 1 is used, the EtherNet/IP scanner transfers parameters
to the module.
For example, if connection 2 is used, the EtherNet/IP scanner transfers no param-
eters to the module, and the port must be configured with a different tool.
8
describes which connection causes EtherNet/
IP scanner parameters to be transferred and which does not.
WAGO Webserver I/O
Field
The
WAGO I/O Field Webserver
is a Webserver that is integrated into the 765
module. Using a Web browser, the user can display the Web pages and display
and modify parameters.
WAGO I/O Field App
The
WAGO I/O Field app
is an app for mobile devices that can communicate with
a 765 module via Bluetooth
®
.
WAGO IO-Link Configura-
tor
WAGO IO-Link Configurator
is software for configuring the WAGO IO-Link mas-
ters and the IO-Link devices.
Three domains are distinguished for configuration and parameterization:
1.
EtherNet/IP configuration
: select EtherNet/IP connection.
2.
Port configuration
: digital input or output
3.
IO-Link device configuration
.
The following table shows which tool can influence which domain.
Table 39: Parameterization Overview
Tool
EtherNet/IP
Connection
Port Configuration
IO-Link Device Configuration
EtherNet/IP
scanner
The EtherNet/
IP scanner con-
figures the Eth-
erNet/IP con-
nection of the
765 module.
The
EtherNet/IP scanner
must be config-
ured to exchange process data with the
modules.
The EDS file wago_0765450x.eds (x = 1 ...
4) describes a WAGO I/O System Field
module. The configuration of the EtherNet/
-