306 Appendix
WAGO-I/O-SYSTEM 750
750-8100 PFC100; 2ETH; ECO
Manual
Version 1.6.0, valid from FW Version 03.02.02(14)
Subsequently the mailbox data are mapped, when the mailbox is permanently
superimposed (Mode 1).
In the operating mode with suppressible mailbox (Mode 2), the mailbox and the
cyclical process data are mapped next.
The following words contain the remaining process dat.
The mailbox and the process image sizes are set with the startup tool
WAGO-I/O-
CHECK
.
Table 259: AS-interface Master Module 750-655, 753-655
Input and Output Process Image
Process
image
size
Offset
Byte Designation
Description
High Byte
Low Byte
12 bytes
0
-
C0/S0
Not used
Control-/
Status byte
1
D1
D0
Mailbox (0, 6, 10, 12 or 18 bytes)/
Process data (0-46 bytes)
…
5
D9
D8
20 bytes
6
D11
D10
…
9
D17
D16
24 bytes *
10
D19
D18
11
D21
D20
32 bytes
12
D23
D22
…
15
D29
D28
40 bytes
16
D31
D30
…
19
D37
D36
48 bytes
12
D39
D38
…
23
D45
D44
*) Factory Setting