0x04 Replace Short Address (Replace_Short_Address)
Replace the short address (DALI addr.) of the ballasts by a new short address
which has not been allocated yet (Parameter 2). Responses to 'Message 4':
- 0xf1: old address not available
- 0xf2: new address already allocated
- 0x01: replacement was successful
0x05 Blink Show Address (Blink)
Initiate cyclical blinking of the ballasts with the assigned address (individual
ballast, group or all). If no further parameter is assigned, the ballasts are
blicking 5 times.
With Parameter 1 the number of flashing sequences can be determined. With
Parameter 2 the period duration is adjusted.
- D1 DALI
Address
- D2
Parameter 2: Duration of one flashing period, resolution: ~600ms
(300ms ON, 300ms OFF), 0x00 = 1 s (default),
0xFF = Switching on one time
- D3
Parameter 1: Number of flashing sequences (1...0xFF, 0x00 = 5
(default))
- D4 0x05
Blink
0x06 Query Short Address available [0-31] (Request_Present_Bit_Low)
Requesting the low present register
- Return channel byte 1: Present bits of ballasts 1 up to 8
- Return channel byte 3: Present bits of ballasts 9 up to 16
- Return channel byte 4: Present bits of ballasts 17 up to 24
- Return channel byte 5: Present bits of ballasts 25 up to 32
0x07 Query Short Address available [32-63] (Request_Present_Bit_High)
Requesting the high present register
- Return channel byte 1: Present bits of ballasts 33 up to 40
- Return channel byte 3: Present bits of ballasts 41 up to 48
- Return channel byte 4: Present bits of ballasts 49 up to 56
- Return channel byte 5: Present bits of ballasts 57 up to 64