750-641 [DALI/DSI Master Module] 

 

 

 Process 

Data 

 

 

  

WAGO-I/O-SYSTEM 

750 

  

I/O 

Modules 

 

0x0C Query Lamp Power On [0-31] 
(Request_Lamp_ArcPowerOn_Bit_Low) 

Requesting the low lamp status register 

-  Return channel byte 1: PowerOn bits of ballasts 1 up to 8 
-  Return channel byte 3: PowerOn bits of ballasts 9 up to 16 
-  Return channel byte 4: PowerOn bits of ballasts 17 up to 24 
-  Return channel byte 5: PowerOn bits of ballasts 25 up to 32 

 

0x0D Query Lamp Power On [32-63] 
(Request_Lamp_ArcPowerOn_Bit_High) 

Requesting the high lamp status register 

-  Return channel byte 1: PowerOn bits of ballasts 33 up to 40 
-  Return channel byte 3: PowerOn bits of ballasts 41 up to 48 
-  Return channel byte 4: PowerOn bits of ballasts 49 up to 56 
-  Return channel byte 5: PowerOn bits of ballasts 57 up to 64 

 

0x0E Setting DALI/DSI Mode and Polling (Set_Feature_Reg)  

Parameter 1 = 0x01:  

The DALI mode is activated, 

   

 

 

polling period is set to default value. 

Parameter 1 = 0x02: 

The DSI mode is activated, 

 

   polling 

is 

deactivated. 

 

0x0F Reset (Reset) 

Double execution of the RESET command with subsequent waiting time 
(500ms). 

 

0x10 Store Scene Level (Store_Actual_Level_As_Scene) 

Write the actual lamp value into the DTR and tranfers this value as scene 
value with the scene number including command number into the variable 
‚Parameter 2‘. 

 

0x11 Store the Polling Period (Set_Polling_Period) 

Store the compound value from Parameter 1 = D3 = Highbyte and Parameter 2 
= D2 = Lowbyte as ‚Polling Period’ in register 39. 

Содержание I/O SYSTEM 750 750-641

Страница 1: ...Fieldbus Independent I O Modules DALI DSI Master Module 750 641 Manual Version 1 2 0...

Страница 2: ...571 8 87 5 55 Fax 49 0 571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the correctness and com pleteness of this documentation However as errors can never be...

Страница 3: ...iption 11 2 1 1 3 Display Elements 12 2 1 1 4 Schematic Diagram 13 2 1 1 5 Technical Data 13 2 1 1 6 Process Data 14 2 1 1 6 1 Implementing a PFC Programming Fieldbus Controller 15 2 1 1 6 2 Implement...

Страница 4: ...ght to provide for any alterations or modifications that serve to increase the efficiency of technical progress WAGO Kontakttechnik GmbH Co KG owns all rights arising from the granting of patents or f...

Страница 5: ...loped for use in an environment that meets the IP20 protection class criteria Protection against finger injury and solid impurities up to 12 5 mm diameter is assured protection against water damage is...

Страница 6: ...Emergency stop functions and equipment shall not be made ineffective See relevant standards e g DIN EN 418 The equipment of your system shall be conform to EMC guidelines so that any electromagnetic i...

Страница 7: ...bserved to ensure smooth and efficient operation ESD Electrostatic Discharge Warning of damage to the components through electrostatic discharge Observe the precautionary measure for handling componen...

Страница 8: ...n a long term basis Warning The components are not resistant against materials having seeping and insulating properties Belonging to this group of materials is e g aerosols silicones triglycerides fou...

Страница 9: ...u e g File New END Pushbuttons are marked as bold with small capitals e g ENTER Keys are marked bold within angle brackets e g F5 Courier The print font for program codes is Courier e g END_VAR 1 6 Nu...

Страница 10: ...e DALI DSI Master Module Attention Accessories required WAGO DC DC converter Item No 288 895 2 1 1 1 View _ 13 14 C D B A 750 641 Bus Bus Bus _ Bus DALI bus U_DALI Data contacts DALI bus DC 18 V DALI...

Страница 11: ...ow for example the wiring of up to 64 DALI slaves directly via one bus line or two parallel bus lines using 2 connectors The module is supplied DC 18 V and common ground connections Warning The WAGO D...

Страница 12: ...ing combination LonWorks Fieldbus Coupler 750 319 together with the WAGO TOPLON IF and PRIO Plug Ins The module is directly supported by the controllers of the WAGO I O SYSTEM 750 A higher level contr...

Страница 13: ...VDE 0712 part 23 DSI Specification TRIDONIC ATCO Specification 2 0 Number of Slaves DALI 64 Number of Slaves DSI 100 Current output max 200 mA Voltage supply DALI DSI 18 V via DC DC converter 288 895...

Страница 14: ...in the document Overview Approvals WAGO I O SYSTEM 750 which you can find on the CD ROM AUTOMATION Tools and Docs Item No 0888 0412 or in the internet under http www wago com Documentation WAGO I O SY...

Страница 15: ...read out using the controller These functions blocks allow for both the Dali commands specified in the standard DIN IEC 60929 and the extended commands to be transmitted and executed Further informat...

Страница 16: ...and Extended Commands 2 1 1 6 2 1Input Data Input data S D0 D1 D2 D3 D4 Status byte DALI response DALI address Message 3 Message 2 Message 1 The response of the Control Byte command is displayed in th...

Страница 17: ...unction Command requests performed by toggling a bit An allocated bit in the status shows that the process is finished This bit takes the value of the request bit Control byte Bit 0 Bit 1 Bit 2 Bit 3...

Страница 18: ...can be transmitted or received by the module 2 IR Init Request IA 0 Init Accepted Resetting the module into the default status The initialization is accomplished only with a rising edge The acknowledg...

Страница 19: ...00 On and step up 9 15 0000 1XXX YAAA AAA1 0 0 0000 0000 Reserved 16 31 0001 XXXX YAAA AAA1 0 0 0000 0000 Go to scene 1 16 32 0010 0000 YAAA AAA1 0 0 0000 0000 Reset 33 0010 0001 YAAA AAA1 0 0 0000 00...

Страница 20: ...y System Failure Level 165 1010 0101 YAAA AAA1 0 0 0000 0000 Query Fade Time Fade Rate 166 175 1010 XXXX YAAA AAA1 0 0 0000 0000 Reserved 176 191 1011 XXXX YAAA AAA1 0 0 0000 0000 Query Scene Level Sc...

Страница 21: ...om Group 1 16 128 Store the DTR as Short Address 129 143 Reserved 144 Bit 0 0 OK Ballast Bit 1 0 OK Lamp Failure Bit 2 0 Off Lamp Power On Bit 3 0 Off Limit Error Bit 4 0 Terminate Fading Bit 5 0 No R...

Страница 22: ...ade Rate 166 175 YAAA AAA1 Reserved 176 191 Lamp Power Level of the Scene XXXX as 8 Bit Number YAAA AAA1 Query Scene Level Scene 1 to 16 192 One bit for each Group LSB Group 0 0 is not associated to t...

Страница 23: ...ess 1AAA AAA1 new Address 0x04 Replace Short Address 5 YAAA AAA1 1 255 0x05 Blink Show Address sec 6 0x06 Query Short Address available 0 31 7 0x07 Query Short Address available 32 63 8 0x08 Query Sta...

Страница 24: ...ress 32 39 Address 40 47 Address 48 55 Address 56 63 Query State Ballast 32 63 0 OK 1 Error 10 Address 0 7 Address 8 15 Address 16 23 Address 24 31 Query Lamp Failure 0 31 0 OK 1 Error 11 Address 32 3...

Страница 25: ...e initialized All search addresses used in the algorithm are sent back on the return channel message 3 5 When a short address is allocated the lamps assigned to this address are lighting When performi...

Страница 26: ...ALI Address D2 Parameter 2 Duration of one flashing period resolution 600ms 300ms ON 300ms OFF 0x00 1 s default 0xFF Switching on one time D3 Parameter 1 Number of flashing sequences 1 0xFF 0x00 5 def...

Страница 27: ...its of ballasts 41 up to 48 Return channel byte 4 Ballast error bits of ballasts 49 up to 56 Return channel byte 5 Ballast error bits of ballasts 57 up to 64 0x0A Query Lamp Failure 0 31 Request_Lamp_...

Страница 28: ...ts of ballasts 41 up to 48 Return channel byte 4 PowerOn bits of ballasts 49 up to 56 Return channel byte 5 PowerOn bits of ballasts 57 up to 64 0x0E Setting DALI DSI Mode and Polling Set_Feature_Reg...

Страница 29: ...xec Device Type Depending Commands 0x13 Response on QUERY ACTUAL LEVEL devices 56 to 59 Request_Level_56_59 Responses on QUERY ACTUAL LEVEL of the devices 56 to 59 Backward channel Byte 1 Level 56 Ini...

Страница 30: ...rse function to 0x15 Backward channel Byte 4 contains the Level Poll Period in msec 2 30 ms 2540 ms 0xFF Off Default Backward channel Byte 3 contains the number of devices polled with QUERY ACTUAL LEV...

Страница 31: ...C converter must be connected to ground using the appropriate FE connection S on the rail The length of the power supply cable between the DC DC converter and the module must not exceed 1 meter Both d...

Страница 32: ...The minimum cross section of the conductors depends on the cable length Cable length Conductor cross section min 100 m 0 5 mm 100 m 150 m 0 75 mm 150 m 1 5 mm Attention The maximum voltage drop of the...

Страница 33: ...the same time is made possible by broadcast addressing Using DALI up to 64 short addresses 16 group addresses and 16 scene light values can be defined Addresses assignement is done using the software...

Страница 34: ...Fade rate System failure level Power on level The electronic ballasts are provided with a logarithmic dimming curve so that adaptation to the eye sensitivity can be achieved Emergency operation setti...

Страница 35: ...750 641 DALI DSI Master Module 35 Notes WAGO I O SYSTEM 750 I O Modules...

Страница 36: ...WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Phone 05 71 8 87 0 Fax 05 71 8 87 1 69 E Mail info wago com Internet http www wago com...

Отзывы: