WAGO I/O SYSTEM 750
Table of Contents
57
750-597 8AO 0-10V/±10V DC
Manual
Version 1.2.0
Table 28:
Calibration
Menu Item
Option
Description
Selection
of the
calibration
method
Enable factory configuration
Enable
factory
configurati
on
*)
Factory calibration is enabled and user calibration is disabled.
Factory calibration is disabled and user calibration is enabled.
Gain
The Gain value is specified by the manufacturer.
Offset
The Offset value is specified by the manufacturer.
Enable user calibration
Enable
user
calibration
User calibration is enabled and factory calibration is disabled.
You determine the gain and offset value yourself.
*)
User calibration is disabled and factory calibration is enabled.
Gain
Enter the Gain value for the user calibration.
The Gain value changes the gain factor of the voltage value.
The resolution is 1/8192.
The value entered must fall in the value range of 0
… 63999.
Offset
Enter the Offset value for the user calibration.
The Offset value moves the zero point of the voltage value (offset
on the y axis).
The resolution is 1 mV per digit.
The value entered must fall in the value range of
−32768 … 32767.
Voltage [V]
Display of the process value in volts (V).
This is a 16-bit value.
The process value is read cyclically from the I/O module.
*)
Factory setting