852-1328
Properties
20
Product manual | Version: 1.2.0
Industrial Managed Switch
4.5.5 Environment requirements
Table 12: Technical Data ‒ Environmental Conditions
Property
Value
Surrounding air temperature, operation
-20 … +70 °C
Surrounding air temperature, storage
-40 … +85 °C
UL 62368-1
Use
Indoor
Pollution degree
PD 2
Relative humidity
5 … 95 %, 55 °C
Vibration resistance
IEC 60068-2-6
Shock resistance
IEC 60068-2-27
EMC immunity to interference
EN 55024
EN 61000-6-2
EN 61000-6-1
EMC Emission of interference
FCC Part 15, Subpart B, Class A,
Class B
EN 55032 Class A and Class B
EN 61000-6-4
EN 61000-6-3
EN 55011
4.6 Guidelines, approvals and standards
4.6.1 Approvals
The following approvals have been granted for the product:
Conformity Marking
Ordinary Locations
UL62368 (E482462)
Note
More information on approvals
You can find detailed information on the approvals online at:
ü
number>
4.6.2 Regulations and Standards
Please observe the standards and regulations that are relevant to installation:
• The data and power lines must be connected and installed in compliance with the stan-
dards to avoid failures on your installation and eliminate any danger to personnel.
• For installation, startup, maintenance and repair, please observe the accident preven-
tion regulations of your machine (e.g., DGUV Regulation “Electrical Installations and
Equipment”).
• Emergency stop functions and equipment must not be deactivated or otherwise made
ineffective. See relevant standards (e.g., EN 418).
• Your installation must be equipped in accordance to the EMC guidelines so electro-
magnetic interferences can be eliminated.