6.3
Parallel Connection (Output Side)
In parallel operation, set the output voltage of the devices that will be connected
in parallel as precisely as possible to the same value. The resistance of the
conductors between the power supply units and the load must be virtually the
same. Only connect devices of the same type in parallel.
Please use external rail-mounted terminal blocks when connecting in parallel. A
parallel connection directly on the connectors of the device’s secondary side is not
allowed.
For decoupling the outputs in parallel mode, the use of diodes in the positive path
is recommended. These diodes must be configured for the device's maximum
output current.