Diagnostics
WAGO-SPEEDWAY 767
767-4801/000-800 8DO 24V DC 0.5A IF (8xM8)
Manual
Version 1.1.0
Pos: 40 /All e Seri en (Allgemei ne Module)/Ü berschriften für alle Serien/Diag nose/Di agnose - Ü berschrift 1 @ 4\mod_1240831069471_21.docx @ 31372 @ 1 @ 1
9
Diagnostics
Pos: 41 /All e Seri en (Allgemei ne Module)/Ü berschriften für alle Serien/Diag nose/LED-Signalisierung - Ü berschrift 2 @ 4\mod_1240831118032_21.docx @ 31375 @ 2 @ 1
9.1
LED Signaling
Pos: 42.1 /Serie 767 (WAGO-SPEED WAY)/Di agnose/I/O-Modul e/Betriebsmel dungen Einl eitung @ 7\mod_1268130796113_21.docx @ 52028 @ @ 1
The following table lists the operating messages that are indicated via LEDs.
Information regarding remedies of certain causes is also provided.
Pos: 42.2 /Serie 767 (WAGO-SPEED WAY)/Wichtige Erläuterungen/Sicherheitshinweise/Hi nweis/Hinweis: 767- 4xxx/- 5xxx Betriebsmeldungen Deakti vierbar e Diag nosen @ 7\mod_1265892089421_21.docx @ 50332 @ @ 1
Disabling specific diagnostics
Use the diagnostic overview (section "Parameterizing" > "Diagnostic Overview")
to disable specific diagnostics (see F- and I/O-LED). In this case, the
corresponding LED is disabled (off).
Pos: 42.3 /Serie 767 (WAGO-SPEED WAY)/Di agnose/I/O-Modul e/Betriebsmel dungen 767- xxxx Abbildung 8xM 8 @ 5\mod_1249454303828_21.docx @ 40393 @ @ 1
Figure 20: LEDs indicating operational messages (exemplary)
Pos: 42.4 /Serie 767 (WAGO-SPEED WAY)/Di agnose/I/O-Modul e/Betriebsmel dungen 767- xxxx Allgemei n (Pos.15, T eil 1) @ 5\mod_1249461825765_21.docx @ 40406 @ @ 1
Table 31: Operating messages 1
Pos. LED Color/Status
Cause
Remedy/information
15
SB
Off
Low voltage;
U
LS
not available.
Check the power supply.
Red, flashing,
4 Hz
S-BUS error on module.
Check whether the S-BUS
cable is connected.
Check the S-BUS cable for
damages.
Check whether the fieldbus
coupler firmware is
compatible with the module.
Red, flashing,
1 or 2 Hz
The module is being restarted
via the fieldbus coupler.
If the flashing frequency is
1Hz, please contact WAGO
Support.
Green
Data exchange is in process;
process data values are valid.
The module is in RUN mode.
-