![WAGO 767-1501 Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/wago/767-1501/767-1501_quick-start-manual_3134275016.webp)
16 Connection
WAGO-SPEEDWAY
767
Fieldbus Coupler for CANopen
Digital inputs:
The sensor cables provide power to the connected sensors and transfer the sensor
signals. The table below outlines the connection assignments for the sensor
connections:
Connection
Contact Description
IN
IN
1
24VDC (supplied from U
LS
)
3 0VDC
1
4
3
X1, X3, X5, X7
1
4
3
X2, X4, X6, X8
4 Input
NOTICE
The highest current carrying capacity of the supply contacts is 4A!
Ensure that the sensors from the U
LS
supply line are supplied with power. The
sensor's power consumption is to be taken into consideration when determining
the present power demand for the U
LS
supply line.
NOTICE
The total maximum power consumption of the sensors must not exceed
400mA (50mA/channel).
Please note that the combined power consumption of all connected sensors is not
to exceed 400mA. The distribution of power among the existing connections is
depending on the individual power requirements of the sensors.