765-4203/0100-0000
Commissioning
92
Product manual | Version: 1.0.0
4PORT IOL-A FLD EC DC 24V 2.0A
Figure 29:
IOL Forcing
Menu Item, “IOL Forcing” Screen
You can find a description of and more information on the forcing function, as well as ex-
planations of terms, in section
8
.
You can use the
forcing
checkbox to specify for each port (X01…X04) in its own row
whether port forcing applies to this port. You can do this separately for the input and out-
put process data.
To enable forcing for a port and enter forcing data (i.e., substitute values) for it, proceed
as follows:
1. Check the
force
box for the port in question.
2. For this port, you can enter 16 byte substitute values in hexadecimal format in the
set value (hexadecimal)
input fields of the column.
Concurrent Access
As long as one user is accessing the forcing functionality through a forcing medium, e.g.,
the WAGO I/O Field Webserver, it is locked for all other users of the module. They cannot
access the forcing functionality until the user that is active now terminates his or her ac-
cess.
In this case, the Web browser displays a message box with the text
“Somebody else
is already forcing. Try again later.”
When the forcing functionality is being
accessed, a small orange icon also appears in the forcing option entry in the menu bar on
the left.