765-4203/0100-0000
Connection
56
Product manual | Version: 1.0.0
4PORT IOL-A FLD EC DC 24V 2.0A
Figure 7: Example of Feeding in and Passing on the Supply Voltages
In connection with this figure, note that the cables illustrated for current paths 1L and 2L
are realized not as separate cables, but rather as separate wires within one common ca-
ble.
Supply Cable and Power Supply (M12)
Take the current load capacities into account. In this regard, see section
8
.
!
NOTICE
Damage to electronics
For passthrough of the supply voltage, the following should be noted:
The maximum total current permitted on 1L is 16 A.
The maximum total current permitted on 2L is 16 A.
The temperature also affects the permissible total current. To take the effects of higher
temperatures into account, note the information on temperature-dependent derating in
section
8
.
Example Calculations
You can find examples for calculating the maximum permissible current feedthrough un-
der
8
To determine whether long cable lengths still supply the product with sufficient voltage,
the voltage losses on the cable can be calculated as follows: