Fieldbus Dependent I/O Module

PROFIBUS

Manual

Technical Description,
Installation and
Configuring

752-121/000-002
Version 1.0.0

Содержание 752-323

Страница 1: ...Fieldbus Dependent I O Module PROFIBUS Manual Technical Description Installation and Configuring 752 121 000 002 Version 1 0 0...

Страница 2: ...h 49 0 571 8 87 5 55 Fax 49 0 571 8 87 4 30 E mail support wago com Every conceivable measure has been taken to ensure the correctness and com pleteness of this documentation However as errors can nev...

Страница 3: ...Module 11 4 1 2 Insertion Extraction of the Electronic Module 12 4 1 3 Marking Label 12 4 1 4 Station address 13 4 2 Electrical Installation 13 4 2 1 General 13 4 2 2 Connection of the Module Supply V...

Страница 4: ...Review 25 7 2 GSD files 25 7 3 Parameterization 26 7 4 Configuration 26 7 5 Diagnosis 27 7 6 Process Data Image 28 7 6 1 Process Data Input Image 29 7 6 2 Process Data Output Image 29 7 7 Fieldbus Co...

Страница 5: ...rred to without reference to patent rights For this reason the existence of such rights cannot be excluded 1 1 2 Personnel Qualification The use of the product described in this manual is solely inten...

Страница 6: ...n in all cases to protect the system from damage Attention Marginal conditions to be observed in all cases to ensure a troublefree opera tion ESD Electrostatic Discharge Warning of danger to the compo...

Страница 7: ...DIx Digital input x DOx Digital output x DSx Diagnostic status for the output group x GSD Ger testammdaten master file of devices PNO PROFIBUS Nutzerorganisation e V User Organisation RTS Request To S...

Страница 8: ...eldbus connection Power supply terminal blocks for internal electronic and external sensors Sensor signal DI Sensor supply Release clip 0V Aktuator signal DO Actuator Supply 0V PROFIBUS RUN BF OVERLOA...

Страница 9: ...T I OUTPUT O 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 0V 24V Fig 2 2 Base Module g1x2306x Fieldbus connection 9 pole D SUB Module power supply terminal bl...

Страница 10: ...allation into the base module If a replacement of the electronic module is necessary the wiring remains undisturbed Status indicators for fast diagnostics The electronic module includes a marking labe...

Страница 11: ...voltage DC 24 V 15 20 Current input module without load 100 mA for 24 V DC Total loss of power 4 5 W Fuse F1 for sensor supply TR5 250 V 6 3A T General information Dimensions W x H x L 155 x 129 x 60...

Страница 12: ...nt 2 mA Short circuit protection electronic automatic restart Max operating frequency without bus resistive load inductive load 1 kHz utilization category DC 13 equals 6 Hz Insulation electronics fiel...

Страница 13: ...inspection Fc 10 57 Hz constant amplitude 0 075 mm 57 150 Hz constant acceleration 1 g Impact According to IEC 60068 2 27 15 g 11 ms Electrical Safety Reverse voltage protection Yes Air and creepage...

Страница 14: ...16 33 33 34 34 35 35 36 36 37 37 38 38 39 39 40 40 41 41 42 42 43 43 44 44 45 45 46 46 47 47 48 48 0V 0V 24V 24V PROFIBUS PROFIBUS READY READY BF BF OVERLOAD OVERLOAD PUSH PUSH PUSH PUSH WAGO I O SYS...

Страница 15: ...6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 17 18 25 26 WAGO I O SYSTEM 752 PROFIBUS 16 DI 16DO ITEM NO Fertigungsnr 13...

Страница 16: ...ng in the electronic module g1x2302x The electronic module is correctly inserted when all four latches have en gaged PROFIBUS RUN BF OVERLOAD PUSH PUSH WAGO I O SYSTEM 752 16DI 16DO 752 323 01 2 3 4 5...

Страница 17: ...unpermissible address 0 the station use the address 126 The station address is taken over by the I O module after power on Changes during the operation have no effect 4 2 Electrical Installation 4 2 1...

Страница 18: ...42 43 44 45 46 47 48 17 18 25 26 WAGO I O SYSTEM 752 PROFIBUS 16 DI 16DO ITEM NO Fertigungsnr 1300 07 04 752 823 INPUT I OUTPUT O 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 33 34 35 36 37 38 39 40 41 42 4...

Страница 19: ...e terminals are available for each digital input The termi nals for one input are shown superimposed 1 2 3 17 18 19 33 34 35 24 V 0 V Input grey Color red blue Supply of the field devices Vertical con...

Страница 20: ...shipped with jumpers installed in each of these termi nals connecting 24VDC module power to connection point for the output supply voltage 24 V 0 V 1 2 3 33 34 35 4 5 6 7 8 17 18 36 37 38 39 40 Output...

Страница 21: ...the terminal blocks This row of terminal blocks will be wired back to the source common of the supply potential 4 2 5 Connection of the Output Signals The output signal terminals are identified by the...

Страница 22: ...ed and screened pair of wires The fieldbus line is specified in EN 50 170 as a line type A and must provide certain line parameters The line type B also described in the EN 50 170 is an old type and s...

Страница 23: ...an be maximum 16 mm 6 6 3 3 1 1 9 9 8 7 2 2 4 4 7 8 5 5 VP 390 390 220 RxD TxD P RxD TxD P RTS RTS RxD TxD N RxD TxD N DGND 9 pole D SUB Connector with Terminating Resistor 9 pole D SUB Connector Furt...

Страница 24: ...2 PROFIBUS 16 DI 16DO INPUT I INPUT I INPUT I INPUT I OUTPUT O OUTPUT O OUTPUT O OUTPUT O PROFIBUS DP PROFIBUS DP PROFIBUS DP PROFIBUS DP RUN RUN BF BF OVERLOAD OVERLOAD WAGO I O SYSTEM 752 16DI 16DO...

Страница 25: ...representation of the input output and supply circuitry are shown in the schematic circuit diagram 100nF 100nF 100nF 100nF 100nF 10nF 0 V 24 V 6 3 A DI 1 16 DO 1 16 DI DO Fieldbus connection Actuator...

Страница 26: ...3 14 15 16 1 2 3 4 5 6 7 8 OUTPUT 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 9 10 11 12 13 14 15 16 3 1 2 Fig 6 1 Status Indicators g1x2305x 1 Fieldbus PROFIBUS specific status indicators...

Страница 27: ...cuit OFF 1 No supply OFF 0 No supply OFF 1 Output switched on 0 Output switched off 6 3 Fieldbus Interface Status Indicators LED Color Status Meaning RUN Operational Green ON OFF The supply voltage is...

Страница 28: ...tage to the output drivers Fault of an output driver Feedback A fault is detected if a transmitted value of 1 by the master controller does not produce a threshold voltage at a corresponding output Wh...

Страница 29: ...ures of the modules are defined by the manu facturers in the form of a GSD file unit basic data Structure content and coding of this unit main data are standardised and made available to the user allo...

Страница 30: ...6 Group allocation 7 0 0 0 0 0 WD 0 0 Watchdog Base 0 Time base 10 ms 1 Time base 1 ms 8 0 0 0 0 0 0 0 0 reserved ever 0 9 0 0 0 0 0 0 0 0 reserved ever 0 10 0 0 0 0 0 0 0 0 reserved ever 0 11 0 0 0...

Страница 31: ...over Byte or word Total length 7 5 Diagnosis The slave diagnosis of the I O module provides 6 Byte standard diagnosis and 7 Byte device status diagnosis Byte Information Meaning 0 Station status 1 1 S...

Страница 32: ...roduce a threshold voltage at a corresponding output When such a fault is detected the electronic module transmits a periphery fault signal to the fieldbus controller board and illuminates the OVERLOA...

Страница 33: ...er board Fieldbus controller boards for programmable logical controls are available from other manufacturers 7 8 Configuration Software Before a PLC can communicate I O data with a fieldbus device the...

Страница 34: ...O 752 102 1 sheet 9 labels Replacement fuse F1 TR 5 250 V 6 3A T Micro fuse according to IEC 127 3 Note Use UL Recognized fuse only 752 180 5 Felt tipped pen for non smudge writing 210 110 1 Operating...

Страница 35: ...n of and access to the decentral fieldbus equipment It is the fieldbus master which co ordinates the bus traffic and transfers the data to a control system Group Input output group connection group Ge...

Страница 36: ...WAGO Kontakttechnik GmbH P O Box 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Telephone 05 71 8 87 0 Telefax 05 71 8 87 1 69 E Mail info wago com Internet http www wago com...