Technical Data
• 7
Fieldbus Dependent I/O Module
PROFIBUS DP
3 Technical Data
PROFIBUS DP System data
Number of nodes
96 with repeatern
Max. no. I /O points
approx. 6000 (depends on master)
Transmission medium
Cu cable according to EN 50 170
Max. length of fieldbus segment
100 m ... 1,200 m (depends on baud rate /on the cable)
Baud rate
9,6 kBaud ... 12 MBaud
Buscoupler connection
9-pole D-SUB, female
Supply
Supply voltage
DC 24 V (– 15 % / + 20 %)
Current input
(module without load)
< 100 mA for 24 V DC
Total loss of power
< 4.5 W
Fuse F1 for sensor supply
TR5 250 V / 6.3A T
General information
Dimensions W x H x L
(155 x 129 x 60
*
) mm
Housing material
polycarbonate
Fixing
Snap mounting onto 35 DIN carrier rail
EN 50022-35
Fitting position
vertical and horizontal
Weight
approx. 500 g
*
from upper edge of DIN 35 rail
Wire connection
Power supply
CAGE CLAMP
®
0.08 mm² ... 2.5 mm², AWG 28-12*
Sensors, actuators
CAGE CLAMP
®
0.08 mm² ... 1.5 mm², AWG 28-16
Supply voltage for
outputs (8 circuit group)
CAGE CLAMP
®
0.08 mm² ... 1.5 mm², AWG 28-16
* AWG12: THHN, TWHN