751-5201 [AS-Interface Module 4IN/4OUT 24V/2A Single]
•
13
Technical Data
WAGO-I/O-SYSTEM 751
AS-Interface Components IP67
2.1.1.7 Technical Data
Tab. 2.1.1-3: Technical Data
Inputs
Number of inputs
4
Sensor supply via AS-Interface control
voltage
max.
200 mA, short-circuit-proof
Current limitation for all inputs
tot.
200
mA
Rated voltage
18 V ... 31 V
PELV from AS-Interface
Input types
IEC 61131 type 1,
+ active 7 mA current sink (type 2)
Signal voltage (0)
≤
5 V
Signal voltage (1)
≥
11 V
Connection system
Socket, M12 x 1, 5-pole
Outputs
Number of outputs
4
Output types
Electronic outputs PNP
Isolation
ASI / AUX
Temporary overload
acc. to EN 61131
Watchdog
(outputs are switched off automatically by
AS-Interface communication errors)
integrated
Current carrying capacity per output
2 A*
* Inductive loads
Utilization category DC 13
Current carrying capacity per module
max.
8
A
External voltage supply (AUX)
acc. to PELV
Rated voltage
24 V (-15 % ... +20 %)
Connection system
socket, M12 x 1, 5-pole