I/O Modules • 165
Process Data Architecture for MODBUS/TCP
WAGO-I/O-SYSTEM 750
Linux Fieldbus Coupler
7.2.6 System Modules
System Modules with Diagnostics
750-610, -611
The 750-610 and 750-611 Supply Modules provide 2 bits of diagnostics in
the Input Process Image for monitoring of the internal power supply.
Input Process Image
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2
Bit 1
Bit 0
Diagnostic bit S 2
Fuse
Diagnostic bit S 1
Voltage
Binary Space Module
750-622
The Binary Space Modules 750-622 behave alternatively like 2 channel
digital input modules or output modules and seize depending upon the
selected settings 1, 2, 3 or 4 bits per channel. According to this, 2, 4, 6 or 8
bits are occupied then either in the process input or the process output
image.
Input or Output Process Image
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
(Data bit
DI 8)
(Data bit
DI 7)
(Data bit
DI 6)
(Data bit
DI 5)
(Data bit
DI 4)
(Data bit
DI 3)
Data bit
DI 2
Data bit
DI 1