122 Diagnostics
WAGO-I/O-SYSTEM 750
753-668/000-004 4FAI 0/4-20 mA Diff PROFIsafe
Manual
Version 1.0.0, valid from HW/SW Version 01/01
Table 49: Diagnostic Messages
Alarm
Description
Error uploading the
iParameters
Diagnostic
type
Module diagnostics
Coding
0x0049
LED indicator
No indicator
Description/
Remedy
Timeout when saving (uploading) the
iParameters to the iPar server. Check
whether an iPar server instance was
created for the F I/O module.
Classification
Error
Firmware update
required
Diagnostic
type
Module diagnostics
Coding
0x0231
LED indicator
Group error red, 2 Hz flashing
Description/
Remedy
Checking the firmware image has resulted
in an inconsistent state. Update the device
firmware.
Classification
Error
Inconsistent
F_iPar_CRC
Diagnostic
type
Module diagnostics
Coding
0x004B
LED indicator
Group error red
PROFIsafe status red
Description/
Remedy
The CRC calculated by the iParameter set
is not identical to the CRC for the
iParameter set transmitted in the
F parameter set. Generate a consistent
combination from the iParameter set and
F parameter set. Check the parameter set
of the iPar server if necessary.
Classification
Error