WAGO-I/O-SYSTEM 750
Functions
61
753-668/000-004 4FAI 0/4-20 mA Diff PROFIsafe
Manual
Version 1.0.0, valid from HW/SW Version 01/01
4.10
Setting the Measurement Range
For the F I/O module, two different measurement ranges can be set for each
individual analog input.
•
0
… 20 mA
•
4
… 20 mA
The settings are made via the “
Measurement Range
” parameter, which is
described in Section “Commissioning” > … > “Setting Parameters”.
Wire break detection can only be parameterized with 4 ... 20 mA!
A wire break detection for each analog input can only be parameterized if the
measurement range 4 ... 20 mA and analog value representation are set to one
of the Siemens S7 formats.