![WAGO 750-624/020-002 Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/wago/750-624-020-002/750-624-020-002_manual_868730023.webp)
WAGO-I/O-SYSTEM 750
Device Description 23
750-626/020-002 Power Supply Filter 24 VDC HI GF
Manual
Version 1.0.0
3.6
Technical Data
3.6.1
Device Data
Table 6: Technical Data — Device
Width
12 mm
Height (from upper edge of DIN-rail)
64 mm
Depth
100 mm
Weight
53 g
3.6.2
Power Supply
Table 7: Technical Data – Power Supply
Supply voltage, system
(24 V)
24 VDC SELV (−25 % ... +30 %)
power supply and transmission
via CAGE CLAMP
®
connection
Supply voltage, system (5 V)
5 VDC (via data contacts)
Current consumption – system supply
(5 V)
typ. 29 mA (ground diagnostics
activated)
Supply voltage, field
24 VDC SELV (−25% ... +30%);
(power supply via CAGE CLAMP
®
-
connection; transmission via spring
contact)
Current consumption, field
Typ. 16 mA (when a ground fault is
detected)
Current
max.
via power jumper contacts
10 A
Current via system voltage
(24 V)
max.
1.5 A (Out)
Isolation
System (24 V) / Field (24 V)
300
VDC (limited by a transient
protection device
)
3.6.3
Ground Fault Diagnostics
Table 8: Technical Data – Ground Fault Diagnostics
Pre-alarm
50 kΩ (+/-15 %)
Main alarm
25 kΩ (+/-15 %)
Hysteresis
Typ. +25…30 %
Response time
<=5 s (typ. 2.5 s)
Internal resistance DC (test circuit)
>10 MΩ (ground diagnostics disabled)
>90 kΩ (ground diagnostics enabled)
Test current
<=180 µA (R
F
=0 Ω)
Permissible system leakage capacitance <=2 µF