WAGO I/O SYSTEM 750 XTR
Connect Devices 35
750-613/040-000 System Power Supply 24 VDC XTR
Manual
Version 1.3.0
5.2
Power Supply Concept
The system power supply and field power supply must be powered via
SELV/PELV power supply units.
The system power supply is fed in via the upper 24 V/0 V CAGE CLAMP
®
connectors in parallel to the coupler/controller and is protected using a joint fuse.
Figure 10: System Supply with a Fieldbus Coupler/Controller (Example)
Resetting the system by switching on and off the system supply
Resetting the system by switching on and off the system supply must take place
simultaneously for all supply modules (field bus coupler/controller and system
supply modules 750-613/040-000)!