WAGO I/O SYSTEM 750 XTR
Mounting 35
750-585/040-000 2AO 0-20mA Ex i XTR
Manual
Version 1.1.0
Don't forget the bus end module!
Always plug a bus end module 750-600/040-000 onto the end of the fieldbus
node! You must always use this bus end module at all fieldbus nodes with the
WAGO I/O SYSTEM 750 XTR fieldbus couplers/controllers to guarantee proper
data transfer.
Pos: 26.6 /Serie 750 (WAGO I/O SYSTEM)/Montieren/Demontieren/I/O-Module 750xxxx/0040xxxx 4g-5g @ 15\mod_1367558844291_21.docx @ 118470 @ @ 1
For vibration loads > 4g, observe the following installation instructions:
•
Use pan-head screws or blind rivets at least every 60 mm (12 mm pin
spacing) to secure the DIN rail.
•
Make the open conductor length between strain relief and wire connection
as short as possible.
•
Use the reinforced end stop 249-197.
Pos: 26.7 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1