750-563 [2 AO 0/4-20mA / 6-18V DC 16 Bit] • 31
Parameter
Setting
WAGO-I/O-SYSTEM 750
I/O Modules
2.1.1.9.4.2 Register Structure
2.1.1.9.4.2.1
Parameter Data (Register 56)
Register 56 contains the parameter data to be read or written. Depending on
the access type, either the I/O module (read parameters) or the fieldbus
coupler (write parameters) will write data to the register.
Register 56 parameter channel register 0
Bit
7
6
5
4
3
2
1
0
Parameter
PRM7
PRM6
PRM5
PRM4
PRM3
PRM2
PRM1
PRM0
Bit
15
14
13
12
11
10
9
8
Parameter
PRM15
PRM14
PRM13
PRM12
PRM11
PRM10
PRM9
PRM8
PRM0 ...
PRM15
Parameter data bit 0 to bit 15
2.1.1.9.4.2.2 Communication Control (Register 57)
Parameter channel control and diagnostics are done via register 57.
Register 57 parameter channel register 1
Bit
7
6
5
4
3
2
1
0
Request
parameter
A7 A6 A5 A4 A3 A2 A1 A0
Response
parameter
A7 A6 A5 A4 A3 A2 A1 A0
Bit
15
14
13
12
11
10
9
8
Request
parameter
TGL_
MS
PRM_R
W
MORE_P
RM
RES RES RES RES RES
Response
parameter
TGL_S
M
TIME
OUT
BUF_O
VF
PRM_E
RR
RES RES RES RES
Request
parameter
Information is written by the application and read by the I/O module
Response
parameter
Information is written by the I/O module and read by the application