20
•
750-563 [2 AO 0/4-20mA / 6-18V DC 16 Bit]
Parameter
Setting
WAGO-I/O-SYSTEM
750
I/O
Modules
2.1.1.9 Parameter Setting
2.1.1.9.1 Register Assignment
The following tables display the assignments and factory settings for the
individual registers. The factory settings are the same for both channels.
Register
Function
Memory Access
Factory setting
17
Manufacturer calibration offset
RAM
R/W
0xXXXX
16 bit integer value with leading sign.
The manufacturer calibration is active if bit 1 is set in register 32.
Y
DAC
= Y
3
* R18 / 8192 + R17
Register
Function
Memory Access
Factory setting
18
Manufacturer calibration gain
RAM
R/W
0xXXXX
16 bit fixed point value without leading sign.
The manufacturer calibration is active if bit 1 is set in register 32.
Y
DAC
= Y
3
* R18 / 8192 + R17
Register
Function
Memory Access
Factory setting
19
Manufacturer substitution value
RAM
R/W
0x0000
16 bit in X
IN
coordinates, depending on the numeric format.
The substitute value is placed on the output of the module after a system reset or a watchdog
timer overflow (module has received no process data for 100 ms).
The substitute value is selected via register 32, bit 9.