WAGO-I/O-SYSTEM 750 XTR 

Use in Hazardous Environments  53 

750-537/040-000 8DO 24 VDC 0.5A Diagn XTR 

 

 

 

Manual 

 

Version 1.1.1  

 

8.2 

Installation Regulations 

 

For the installation and operation of electrical equipment in hazardous areas, the 

valid national and international rules and regulations which are applicable at the 

installation location must be carefully followed. 

 

 

 

8.2.1 

Special Notes including Explosion Protection 

 

The following warning notices are to be posted in the immediately proximity of the 

WAGO I/O SYSTEM 750 (hereinafter “product”): 

WARNING – DO NOT REMOVE OR REPLACE FUSED WHILE ENERGIZED! 

WARNING – DO NOT DISCONNECT WHILE ENERGIZED! 

WARNING – ONLY DISCONNECT IN A NON-HAZARDOUS AREA! 

Before using the components, check whether the intended application is 

permitted in accordance with the respective printing. Pay attention to any 

changes to the printing when replacing components. 

The product is an open system. As such, the product must only be installed in 

appropriate enclosures or electrical operation rooms to which the following 

applies: 

• 

Can only be opened using a tool or key 

• 

Inside pollution degree 1 or 2 

• 

In operation, internal air temperature within the range of 0 

°C

 

 Ta 

 +55 

°C 

or −20

 

°C

 

 Ta 

 +60 

°C for co

mponents with extension number …/025-xxx 

or −40

 

°C

 

 Ta 

 +70 

°C for components with extension number …/040

-xxx 

• 

Minimum degree of protection: min. IP54 (acc. to EN/IEC 60529) 

• 

For use in Zone 2 (Gc), compliance with the applicable requirements of the 

standards EN/IEC/ABNT NBR IEC 60079-0, -7, -11, -15 

• 

For use in Zone 22 (Dc), compliance with the applicable requirements of 

the standards EN/IEC/ABNT NBR IEC 60079-0, -7, -11, -15 and -31 

• 

For use in mining (Mb), minimum degree of protection IP64 (acc. EN/IEC 

60529) and adequate protection acc. EN/IEC/ABNT NBR IEC 60079-0 and 

-1 

• 

Depending on zoning and device category, correct installation and 

compliance with requirements must be assessed and certified by a “Notified 

Body” (ExNB) if necessary! 

Содержание 750-537/040-000

Страница 1: ...Manual WAGO I O SYSTEM 750 XTR 750 537 040 000 8DO 24 VDC 0 5A Diagn XTR 8 Channel digital Output 24 VDC 0 5 A Diagnostics Extreme Version 1 1 1...

Страница 2: ...84 45 55 E Mail support wago com Every conceivable measure has been taken to ensure the accuracy and completeness of this documentation However as errors can never be fully excluded we always appreci...

Страница 3: ...kaging 11 2 2 Safety Advice Precautions 12 3 Device Description 15 3 1 View 18 3 2 Connectors 19 3 2 1 Data Contacts Local Bus 19 3 2 2 Power Jumper Contacts Field Supply 20 3 2 3 CAGE CLAMP Connector...

Страница 4: ...or F I O Modules 44 7 2 1 General Structure of a Potential Group 44 8 Use in Hazardous Environments 45 8 1 Marking Configuration Examples 46 8 1 1 Marking for Europe According to ATEX and IECEx 46 8 1...

Страница 5: ...d in the manual for the used fieldbus coupler controller Consider power layout of the WAGO I O SYSTEM 750 XTR In addition to these operating instructions you will also need the system description Desi...

Страница 6: ...ndicates a moderate risk potentially hazardous situation which if not avoided could result in death or serious injury Personal Injury Indicates a low risk potentially hazardous situation which if not...

Страница 7: ...R Notes about this Documentation 7 750 537 040 000 8DO 24 VDC 0 5A Diagn XTR Manual Version 1 1 1 Additional Information Refers to additional information which is not an integral part of this document...

Страница 8: ...data files are marked in italic type e g C Program Files WAGO Software Menu Menu items are marked in bold letters e g Save A greater than sign between two names means the selection of a menu item fro...

Страница 9: ...All changes to the coupler or controller should always be carried out by qualified personnel with sufficient skills in PLC programming 2 1 3 Use of the 750 Series in Compliance with Underlying Provis...

Страница 10: ...he user The following actions will result in the exclusion of liability on the part of WAGO Kontakttechnik GmbH Co KG Repairs Changes to the hardware or software that are not described in the operatin...

Страница 11: ...lectrical and electronic equipment can be harmful to the environment and human health 2 1 4 1 2 Packaging Packaging contains materials that can be reused PPWD 94 62 EU and 2004 12 EU packaging guideli...

Страница 12: ...tion against contact Prevent fire from spreading outside of the enclosure Offer adequate protection against UV irradiation Guarantee mechanical stability Restrict access to authorized personnel and ma...

Страница 13: ...ce Replace defective or damaged devices Replace defective or damaged device module e g in the event of deformed contacts Protect the components against materials having seeping and insulating properti...

Страница 14: ...ectrostatic discharge per DIN EN 61340 5 1 3 When handling the devices please ensure that environmental factors personnel work space and packaging are properly grounded Use only direct current DC for...

Страница 15: ...ctronic components of the I O module can be damaged by the induced voltage produced when inductive loads are de activated An appropriate protection circuit e g a recovery diode must be installed in pa...

Страница 16: ...mage Using this bit the master control can identify the error After rectifying the error the error bit is reset in the input image and the error LED goes off The field voltage and the system voltage a...

Страница 17: ...24 VDC 0 5A Diagn XTR Manual Version 1 1 1 The I O module can be operated with all fieldbus couplers controllers of the WAGO I O SYSTEM 750 XTR Observe the instructions for mixed operation when used...

Страница 18: ...for Figure View Pos Description Details See Section 1 Marking possibility with Mini WSB 2 Status LEDs Device Description Display Elements 3 Data contacts Device Description Connectors 4 CAGE CLAMP co...

Страница 19: ...ich are available as self cleaning gold spring contacts Figure 2 Data Contacts Do not place the I O modules on the gold spring contacts Do not place the I O modules on the gold spring contacts in orde...

Страница 20: ...igure 3 Power Jumper Contacts Table 4 Legend for Figure Power Jumper Contacts Contact Type Function 1 Spring contact Potential transmission Uv for field supply 2 Spring contact Potential transmission...

Страница 21: ...le 5 Legend for Figure CAGE CLAMP Connectors Channel Designation Connector Function 1 DO 1 1 Output DO 1 Signal voltage 2 DO 2 5 Output DO 2 Signal voltage 3 DO 3 2 Output DO 3 Signal voltage 4 DO 4 6...

Страница 22: ...Status DO 5 C Error DO 5 6 Status DO 6 G Error DO 6 7 Status DO 7 D Error DO 7 8 Status DO 8 H Error DO 8 Table 7 Display Element Diagnostics per Channel LED Status Output Target Condition Explanatio...

Страница 23: ...WAGO I O SYSTEM 750 XTR Device Description 23 750 537 040 000 8DO 24 VDC 0 5A Diagn XTR Manual Version 1 1 1 3 4 Schematic Diagram Figure 6 Schematic Diagram...

Страница 24: ...max 80 mA Current consumption power jumper contact typ 24 VDC 16 mA per module load Voltage supply via power jumper contacts under laboratory conditions for ambient operating temperature 40 C 55 C fo...

Страница 25: ...typ PWM 12 A Open circuit detection in OFF state 0 1 mAtyp at 24 V 1 0 mA No open circuit Diagnostics Open circuit overload and short circuit 3 5 5 Connection Type Table 12 Technical Data Field Wirin...

Страница 26: ...00 m 5000 m 0 5 K per 100 m 5000 m Resistance to harmful substances Acc to IEC 60068 2 42 and IEC 60068 2 43 Maximum pollutant concentration at relative humidity 75 SO2 25 ppm H2S 10 ppm Special condi...

Страница 27: ...CULUS UL61010 2 201 The following approvals are pending for the 750 537 040 000 I O module Korea Certification The following Ex approvals are pending for the 750 537 040 000 I O module CULUS UL 12 12...

Страница 28: ...C 0 5A Diagn XTR Manual Version 1 1 1 More information about approvals Detailed references to the approvals are listed in the document Overview Approvals WAGO I O SYSTEM 750 which you can find via the...

Страница 29: ...ectrical equipment Equipment requirements in the types of protection EN 60079 7 Electrical equipment in e type of protection with ec level of protection EN 60079 15 Electrical equipment in the n type...

Страница 30: ...0 shocks per axis and direction half sine EN 50155 EN 61373 Random vibration Category 1 classes A and B Shock 5g 30 ms Category 1 classes A and B Environmental Requirements EN 61850 3 Achieved EN 6072...

Страница 31: ...nces Burst EN 61000 4 4 EN 60255 26 IEEE C37 90 1 4 kV Surge Voltage Surge EN 61000 4 5 EN 60255 26 1 kV conductor conductor 2 kV conductor ground Conducted Disturbances Induced by High frequency Fiel...

Страница 32: ...nsure proper function in the event of line frequency disturbances in accordance with EN 61000 4 16 or EN 60255 26 Line Frequency Disturbance Variables with respect to the power supply shielded cables...

Страница 33: ...6 GHz 60 dB V m AV 3 GHz 6 GHz Shipbuilding Class B 80 dB V m 50 dB V m QP 150 kHz 300 kHz 50 dB V m 34 dB V m QP 0 3 MHz 30 MHz 54 dB V m QP 30 MHz 2 GHz 24 dB V m QP 156 MHz 165 MHz Shipbuilding Cla...

Страница 34: ...EMC A or EMC B Table 21 Standards and Rated Conditions for Rail Applications EN 50155 Class Standard Compliance 4 1 Rated Operating Conditions 4 1 1 Altitude above sea level AX EN 50125 1 4 1 2 Ambie...

Страница 35: ...igital output channel 2 DO 3 Signal state DO 3 Digital output channel 3 DO 4 Signal state DO 4 Digital output channel 4 DO 5 Signal state DO 5 Digital output channel 5 DO 6 Signal state DO 6 Digital o...

Страница 36: ...are sharp edged Handle the I O module carefully to prevent injury Do not touch the blade contacts Insert I O modules only from the proper direction All I O modules feature grooves for power jumper co...

Страница 37: ...k when devices are energized High voltage can cause electric shock or burns Switch off all power to the device prior to performing any installation repair or maintenance work Temperature range applies...

Страница 38: ...rier rail Figure 8 Snap the I O Module into Place Example With the I O module snapped in place the electrical connections for the data contacts and power jumper contacts if any to the fieldbus coupler...

Страница 39: ...TR Mounting 39 750 537 040 000 8DO 24 VDC 0 5A Diagn XTR Manual Version 1 1 1 Figure 9 Removing the I O Module Example Electrical connections for data or power jumper contacts are disconnected when re...

Страница 40: ...o each CAGE CLAMP Do not connect more than one conductor at one single connection If more than one conductor must be routed to one connection these must be connected in an up circuit wiring assembly f...

Страница 41: ...WAGO I O SYSTEM 750 XTR Connect Devices 41 750 537 040 000 8DO 24 VDC 0 5A Diagn XTR Manual Version 1 1 1 6 2 Connection Example Figure 11 Connection Example 1 Conductor Connection...

Страница 42: ...1 Important Notes Only operate interference free I O modules at a safe extra low voltage When using interference free I O modules only use power supplies with protective extra low voltage PELV SELV f...

Страница 43: ...y switching device Reverse supply must absolutely be avoided Avoid short circuits between outputs Short circuits between outputs of different interference free digital output modules must absolutely b...

Страница 44: ...to a safety switching device shall be combined to form a potential group The power supply of the potential group may only be provided via the following supply or filter modules Table 24 Supply or Fil...

Страница 45: ...azardous areas and shall be used in accordance with the marking and installation regulations The following sections include both the general identification of components devices and the installation r...

Страница 46: ...040 000 8DO 24 VDC 0 5A Diagn XTR Manual Version 1 1 1 8 1 Marking Configuration Examples 8 1 1 Marking for Europe According to ATEX and IECEx Figure 13 Marking Example According to ATEX and IECEx Fi...

Страница 47: ...Explosion group of dust T135 C Max surface temperature of the enclosure without a dust layer Dc Equipment protection level EPL Mining I Equipment group Mining M2 Category High level of protection Ex E...

Страница 48: ...750 XTR 750 537 040 000 8DO 24 VDC 0 5A Diagn XTR Manual Version 1 1 1 Figure 15 Marking Example for Approved Ex i I O Module According to ATEX and IECEx Figure 16 Text Detail Marking Example for Appr...

Страница 49: ...st layer Dc Equipment protection level EPL Mining I Equipment Group Mining M2 M1 Category High level of protection with electrical circuits which present a very high level of protection Ex Explosion p...

Страница 50: ...ates of America NEC and Canada CEC Figure 17 Marking Example According to NEC Figure 18 Text Detail Marking Example According to NEC 500 Table 27 Description of Marking Example According to NEC 500 Ma...

Страница 51: ...t protection level EPL Associated apparatus with intrinsic safety circuits for use in Zone 20 IIC Group T4 Temperature class Gc Equipment protection level EPL Figure 20 Text Detail Marking Example for...

Страница 52: ...k nA Type of protection ia IIIC Type of protection and equipment protection level EPL Associated apparatus with intrinsic safety circuits for use in Zone 20 IIC Group T4 Temperature class Gc Equipment...

Страница 53: ...g when replacing components The product is an open system As such the product must only be installed in appropriate enclosures or electrical operation rooms to which the following applies Can only be...

Страница 54: ...particular Operating DIP switches coding switches or potentiometers Replacing fuses Wiring connecting or disconnecting of non intrinsically safe circuits is only permitted in the following cases The...

Страница 55: ...ephone networks or telecommunication cables WARNING The radio receiver module 750 642 may only be used to connect to external antenna 758 910 WARNING Product components with fuses must not be fitted i...

Страница 56: ...etting up a Potential Group Example 44 Figure 13 Marking Example According to ATEX and IECEx 46 Figure 14 Text Detail Marking Example According to ATEX and IECEx 46 Figure 15 Marking Example for Appro...

Страница 57: ...al Conditions 26 Table 17 Standards and Rated Conditions for Explosion Protection Applications 29 Table 18 Climatic and Mechanical Environmental Conditions and Shipbuilding 30 Table 19 EMC Immunity to...

Страница 58: ...WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Phone 49 571 887 0 Fax 49 571 887 844169 E Mail info wago com Internet www wago com...

Отзывы: