Description • 3

Application note
A206000

2 Description

This application describes the operation of the WAGO 750-312 Buscoupler
with the WinTech (TM) Modbus Scanner software. This note also describes a
typical 4 wire connection diagram to a standard RS-232  port utilizing a RS-
232 to RS-485 converter on a DOS based computer running Windows 95 and
NT.

3 Reference Material

WAGO Modbus Manual  750-138

Modbus Protocol (obtained from WAGO application engineers)

Hardware Required

DOS Based Computer with Windows 95 or NT

Modbus Buscoupler 750-312, any I/O and end module 750-600

B&B Electronics RS-232 to RS-485 converter

Misc. cables DB connectors and hoods

4 Solution

4.1  1.

Connect the WAGO 750-650

COMPUTER

B&B

750-312

     

RS-232 / 485

  Pin to Pin of B&B converter

TD(a)------------------------------- 7
TD(b)--------------------------------2
RD(a)--------------------------------8
RD(b)--------------------------------3
SHIELD-----------------------------5

*

Note:  Utilize the manual provided  by WAGO as a reference for 

this procedure.

Содержание 750-312

Страница 1: ...750 312 Modbus Buscoupler Getting started Application note A206000 English Version 1 0 0...

Страница 2: ...e 49 0 571 8 87 5 55 Fax 49 0 571 8 87 4 30 E Mail support wago com Every conceivable measure has been taken to ensure the correctness and com pleteness of this documentation However as errors can nev...

Страница 3: ...1 2 Personnel qualification 1 1 1 3 Intended use 1 1 2 Range of validity 2 2 Description 3 3 Reference Material 3 4 Solution 3 4 1 1 Connect the WAGO 750 650 3 4 2 Configure the Buscoupler 4 4 3 Inst...

Страница 4: ...iv Table of Contents Application note A206000...

Страница 5: ...nual is exclusively geared to spe cialists having qualifications in PLC programming electrical specialists or persons instructed by electrical specialists who are also familiar with the valid standard...

Страница 6: ...ated hardware and software of the spe cific manufacturer as well as the correspondent documentation This applica tion note is therefore only valid for the described installation New hardware and softw...

Страница 7: ...ndows 95 and NT 3 Reference Material WAGO Modbus Manual 750 138 Modbus Protocol obtained from WAGO application engineers Hardware Required DOS Based Computer with Windows 95 or NT Modbus Buscoupler 75...

Страница 8: ...buscoupler for 19 2 K Baud extended function mode Watch dog ON 3x end of frame error check ON 4 3 Installation of the WinTech TM Modscan software this software can be obtained from Win Tech Software...

Страница 9: ...a 17 second communication scan and turns all outputs to OFF From the User Defined Command String screen place a 06 in the Function field Place the hex value of 10 00 00 AA in the Send Data field 17 s...

Страница 10: ...WAGO Kontakttechnik GmbH Postfach 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Telefon 05 71 8 87 0 Telefax 05 71 8 87 1 69 E Mail info wago com Internet http www wago com...

Отзывы: