WAGO I/O SYSTEM 750 XTR
Device Description 19
750-1416/040-000 8DI 24 VDC 0.2ms 2-wire XTR
Manual
Version 1.1.0
Do not exceed maximum values via power contacts!
The maximum current that can flow through the power jumper contacts is 10 A.
The power jumper contacts can be damaged and the permissible operating
temperature can be exceeded by higher current values.
When configuring the system, do not exceed the permissible maximum current
value. If there is a higher power requirement, you must use an additional supply
module to provide the field voltage.
Pos: 32 /D okumentation allgemei n/Glieder ungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1
Pos: 33 /Serie 750 ( WAGO-I/O-SYST EM)/Ger ätebeschrei bung (alte Str uktur)/Anschlüsse/Push-in C AGE C LAM P®-Anschlüsse - Überschrift 3 @ 15\mod_1370519905692_21.docx @ 122018 @ 3 @ 1
3.2.3
Push-in CAGE CLAMP
®
Connectors
Pos: 34 /Serie 750 ( WAGO-I/O-SYST EM)/Wichtige Erläuterungen (al te Str uktur)/Sicherheits- und sonstige Hinweise/War nung/War nung: Speisung ausschließlich aus SELV-/PELV-Versorgung (24V- XTR-I/O-Modul e) @ 29\mod_1493107132163_21.docx @ 419618 @ @ 1
Power from SELV/PELV power supply only!
All field signals and field supplies connected to this XTR I/O module
(750-1416/040-000) must be powered from SELV/PELV power supply(s)!
Pos: 35 /Serie 750 ( WAGO-I/O-SYST EM)/Ger ätebeschrei bung (alte Str uktur)/Anschlüsse/DI/Anschl üsse 750- 141x 8 D I 2-Leiter H SS Push-in C AGE C LAMP @ 7\mod_1274262794032_21.docx @ 56626 @ @ 1
Figure 4: Push-in CAGE CLAMP
®
Connectors
Table 5: Legend for Figure “Push-in CAGE CLAMP
®
Connectors”
Channel Designation Connector Function
1
DI 1
1
Input DI 1: Signal voltage
24 V
9
Input DI 1: Sensor 24 V
2
DI 2
2
Input DI 2: Signal voltage
24 V
10
Input DI 2: Sensor 24 V
.
.
.
7
DI 7
7
Input DI 7: Signal voltage
24 V
15
Input DI 7: Sensor 24 V
8
DI 8
8
Input DI 8: Signal voltage
24 V
16
Input DI 8: Sensor 24 V