14 Device Description
WAGO I/O SYSTEM 750 XTR
750-1416/040-000 8DI 24 VDC 0.2ms 2-wire XTR
Manual
Version 1.1.0
Pos: 18 /All e Seri en (Allgemei ne Module)/Ü berschriften/Ebene 1/Gerätebeschr eibung - Ü berschrift 1 @ 3\mod_1233756084656_21.docx @ 27096 @ 1 @ 1
3
Device Description
Pos: 19.1 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebeschrei bung (alte Str uktur)/Ei nleitung/Anwendung/DI/Anwendung 750- x4xx DI @ 3\mod_1233762736718_21.docx @ 27108 @ @ 1
The digital input module 750-1416/040-000 (8DI 24 VDC 0.2ms 2-wire XTR)
receives control signals from digital field (e.g. of sensors, transmitters, switches
or proximity switches).
Pos: 19.2 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebeschrei bung (alte Str uktur)/Ei nleitung/I/O-Beschrei bung/DI/I/O-Beschr eibung 750- 141x 8 DI 2-Leiter (DI und 24 V) Push-in C AGE C LAM P @ 15\mod_1370934995007_21.docx @ 122344 @ @ 1
The I/O module has 8 input channels, providing a direct connection to 2-wire
sensors.
The sensors are connected to the Push-in CAGE CLAMP
®
connectors DI 1 and
24 V … DI 8 and 24 V.
Pos: 19.3 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebeschrei bung (alte Str uktur)/Ei nleitung/I/O-Beschrei bung/Allgemein/Ver weis auf Kapi tel " Anschl üsse" @ 8\mod_1276775378035_21.docx @ 57956 @ @ 1
The assignment of the connections is described in the “Connectors” section.
Pos: 19.5 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebeschrei bung (alte Str uktur)/Ei nleitung/I/O-Beschrei bung/DI/I/O-Beschr eibung 750- x4xx DI RC-Filter 0,2 ms @ 3\mod_1233755181796_21.docx @ 27083 @ @ 1
Each input channel has a RC noise rejection filter with a time constant of 0.2 ms.
Pos: 19.6 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebeschrei bung (alte Str uktur)/Ei nleitung/I/O-Beschrei bung/DI/I/O-Beschr eibung 750- x4xx DI H SS / positi vschaltend (24 V) @ 3\mod_1233831724648_21.docx @ 27231 @ @ 1
The I/O module inputs provide high-side switching. If the 24 V potential for field
power is switched to an input connection, the signal status for the corresponding
input channel is set to “high”.
Pos: 19.7 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebeschrei bung (alte Str uktur)/Ei nleitung/LED-Anzeige/LED Zustand Signal @ 3\mod_1233755258578_21.docx @ 27087 @ @ 1
A green LED indicates the switched status of each channel.
Pos: 19.8 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebeschrei bung (alte Str uktur)/Ei nleitung/LED-Anzeige/Ver weis auf Kapitel "Anzeigeel emente" @ 5\mod_1246010525000_21.docx @ 36194 @ @ 1
The meaning of the LEDs is described in the “Display Elements” section.
Pos: 19.9 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebeschrei bung (alte Str uktur)/Ei nleitung/Versorgung/Versorgung 24 V, 0 V über Leistungskontakte Standard @ 3\mod_1226498974531_21.docx @ 25020 @ @ 1
The I/O module 750-1416/040-000 (8DI 24 VDC 0.2ms 2-wire XTR) receives the
24 V voltage supply for the field level from an upstream I/O module or from the
fieldbus coupler/controller via blade-formed power jumper contacts. It then
provides these potentials to subsequent I/O modules via spring-formed power
jumper contacts.
Pos: 19.10 /Serie 750 ( WAGO-I/O-SYST EM)/Wichtig e Erl äuter ung en (alte Struktur)/Sicher heits- und sonstige Hi nweise/Warnung/Warnung: Speisung ausschli eßlich aus SELV-/PELV- Versorgung ( 24V-XTR-I/O-M odule) @ 29\mod_1493107132163_21.docx @ 419618 @ @ 1
Power from SELV/PELV power supply only!
All field signals and field supplies connected to this XTR I/O module
(750-1416/040-000) must be powered from SELV/PELV power supply(s)!
Pos: 19.11 /Serie 750 ( WAGO-I/O-SYST EM)/Wichtig e Erl äuter ung en (alte Struktur)/Sicher heits- und sonstige Hi nweise/Achtung/Achtung: Maxi maler Str om Leistungskontakte 10 A @ 3\mod_1226499143500_21.docx @ 25029 @ @ 1
Do not exceed maximum values via power contacts!
The maximum current that can flow through the power jumper contacts is 10 A.
The power jumper contacts can be damaged and the permissible operating
temperature can be exceeded by higher current values.
When configuring the system, do not exceed the permissible maximum current
value. If there is a higher power requirement, you must use an additional supply
module to provide the field voltage.
Pos: 19.12 /Serie 750 ( WAGO-I/O-SYST EM)/Wichtig e Erl äuter ung en (alte Struktur)/Sicher heits- und sonstige Hi nweise/Hi nweis/Hinweis: Potential einspeisemodul für Erde einsetzen! ( kei ne LK für Erde) @ 3\mod_1226499037468_21.docx @ 25023 @ @ 1