WAGO I/O SYSTEM 750 XTR
Device Description 15
750-1416/040-000 8DI 24 VDC 0.2ms 2-wire XTR
Manual
Version 1.1.0
Use supply modules for ground (earth)!
The I/O module has no power jumper contacts for receiving and transmitting the
earth potential. Use a supply module when an earth potential is needed for the
subsequent I/O modules.
Pos: 19.13 /Serie 750 ( WAGO-I/O-SYST EM)/Gerätebeschr eibung (alte Struktur)/Einl eitung/Versorgung/Gal vanische Trennung F eld/System @ 3\mod_1233756478750_21.docx @ 27102 @ @ 1
The field voltage and the system voltage are electrically isolated from each other.
Pos: 19.14 /Serie 750 ( WAGO-I/O-SYST EM)/Gerätebeschr eibung (alte Struktur)/Einl eitung/Versorgung/Anor dnung unter Ber ücksichtigung der Leistungskontakte beliebig @ 3\mod_1233756233468_21.docx @ 27099 @ @ 1
With consideration of the power jumper contacts, the individual modules can be
arranged in any combination when configuring the fieldbus node.
An arrangement in groups within the group of potentials is not necessary.
Pos: 19.15 /Serie 750 ( WAGO-I/O-SYST EM)/Wichtig e Erl äuter ung en (alte Struktur)/Sicher heits- und sonstige Hi nweise/Hi nweis/Hinweis: XTR - Mischbetrieb XTR/Standard @ 15\mod_1367496420828_21.docx @ 118326 @ @ 1
Mixed operation
Mixed operation (standard/XTR modules) within a node is possible when groups
of modules are electrically isolated on the field side (i.e., electrically isolated
power supply).
Pos: 19.16 /Serie 750 ( WAGO-I/O-SYST EM)/Wichtig e Erl äuter ung en (alte Struktur)/Sicher heits- und sonstige Hi nweise/Hi nweis/Hinweis: XTR - Er höhte Störfestig keit @ 15\mod_1367496424993_21.docx @ 118330 @ @ 1
Increased interference!
For standard-compliant application in substation instrumentation and control,
telecontrol systems, railway technology or shipbuilding certified operation,
field-side power supply filter 750-624/040-001 or power supply filter
750-626/040-000 are generally to be used for XTR module groups.
Pos: 19.17 /Serie 750 ( WAGO-I/O-SYST EM)/Gerätebeschr eibung (alte Struktur)/Einl eitung/Einsatzbereich/Einsatzbereich 750- xxxx/040-000 all e XTR-Koppler/Contr oller ohne Ei nschränkung+Mischbetriebhinweise @ 15\mod_1368425919479_21.docx @ 119444 @ @ 1
The I/O module can be operated with all fieldbus couplers/controllers of the
WAGO I/O SYSTEM 750 XTR.
Observe the instructions for mixed operation when used in mixed operation
behind standard fieldbus couplers/controllers.
Pos: 20 /D okumentation allgemei n/Glieder ungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1