2787-2344 (/0000-00x0)
Properties
26
Product manual | Version: 1.0.1
Power Supply Pro 2
Table 35: Standards: EMC – Emission of Interference
Standard
Title
EN IEC 61204-3
Low-Voltage Switch Mode Power Supplies – Part 3: Electromagnetic Com-
patibility (EMC)
EN 61000-6-3
Part 6-3: Generic standards – Emission standard for residential, commercial
and light-industrial environments
Table 36: Standards: LVD – Low Voltage Directive
Standard
Title
EN IEC 61010-2-201
Safety requirements for electrical equipment for measurement, control, and
laboratory use - Part 2-201: Particular requirements for control equipment
EN 61010-1
Safety requirements for electrical equipment for measurement, control, and
laboratory use - Part 1: General requirements
The following tests have been performed in accordance with the EMC standards listed:
Table 37: Standards: EMC – Immunity to Interference (Tests Performed)
Standard
Title
Test
Value
Category
EN 61000-4-2
Part 4-2: Testing and measurement
techniques – Electrostatic discharge
immunity test
Contact discharge
6 kV
B
Air discharge
2 kV/4 kV/8 kV
B
EN 61000-4-3
Part 4-3: Testing and measurement
techniques – Radiated, radio-fre-
quency, electromagnetic field immu-
nity test
80 MHz … 1.0 GHz
(1 kHz AM 80 %)
10 V/m
A
1.0 … 2.0 GHz
(1 kHz AM 80 %)
10 V/m
A
2.0 … 6.0 GHz
(1 kHz AM 80 %)
10 V/m
A
EN 61000-4-4
Part 4-4: Testing and measurement
techniques – Electrical fast transient/
burst immunity test
AC input
2 kV, 5 kHz/100 kHz,
5 min.
A
DC output
2 kV, 5 kHz/100 kHz,
5 min.
A
DC OK/
digital input/
digital output
1 kV, 5 kHz/100 kHz,
5 min.
A
Communication
1 kV, 5 kHz/100 kHz,
5 min.
A
EN 61000-4-5
Part 4-5: Testing and measurement
techniques – Surge immunity test
L → L
1 kV
B
L → PE
2 kV
B
L+ → L−
0.5 kV
B
L+ → PE
L− → PE
1 kV
B
DC OK/
digital input/
digital output → PE
1 kV
B
EN 61000-4-6
Part 4-6: Testing and measurement
techniques – Immunity to conducted
disturbances, induced by radio-fre-
quency fields
AC input
0.15 … 80 MHz:
10 V
A
DC output
0.15 … 80 MHz:
10 V
A
DC OK/
digital input/
digital output
0.15 … 80 MHz:
10 V
A
Communication
0.15 … 80 MHz:
10 V
A