2787-2344 (/0000-00x0)
Properties
20
Product manual | Version: 1.0.1
Power Supply Pro 2
Property
Value
Power Boost
7.5 A (5 s)
Top Boost
30 A (15 ms)
Derating of output power
See section Derating
Line regulation
2)
< 0.05 %
Load regulation
3)
< 2.0 %
Residual ripple/noise
4)
< 25 mV
Overload behavior
5) 6)
“Constant Current” Mode
1)
“Constant Current with Latching Shutdown” Mode
“Hiccup” Mode
“Electronic Circuit Breaker” Mode
“Latching Shutdown on Thermal Overload” Mode
“Power Boost” Mode
“Top Boost” Mode
Switch-on delay (typ.)
6) 7)
400 VAC
1.5 s
1)
Factory setting
2)
Nominal load, in range 340 … 550 VAC
3)
10 % / 90 % load step
4)
20 MHz bandwidth
5)
See section
8
Short-Circuit and Overload Behavior [
6)
Can be set via the WAGO Interface Configuration software
7)
See figure “Turn-on Time”
Overshoot
Turn on Time
Input
Voltage
Output
Voltage
Figure 10: Turn-on Time
!
NOTICE
Select conductor cross-sections according to current load!
In the event of a fault, the output current of a power supply can be up to 1.5 × I
OUT
. Only
use conductor cross-sections sufficient for the current load!
Table 21: Technical Data – Output Connection
Property
Value
Cross-section
Solid
0.08 … 2.5 mm² / 28 … 12 AWG
Fine-stranded
0.08 … 2.5 mm² / 28 … 12 AWG
Insulated ferrule with plastic collar
0.25 … 1.5 mm² / 20 … 16 AWG
Ferrule without plastic collar
0.25 … 2.5 mm² / 20 … 14 AWG
Strip length
8 … 9 mm / 0.31 … 0.35 inch