16
PEA-C4-HiCoat
OPERATING MANUAL
VERSION 05/2012
ORDER NUMBER DOC 390829
4.4
PROTECTIVE AND MONITORING EQUIPMENT
4.4.1
RELEASE GUNS (HIGH-VOLTAGE/PNEUMATIC SYSTEM)
Enabling high-voltage depends on:
Exhaust air is OK
Fire extinguishing system/fi re detection system is OK (external signal)
No EMERGENCY STOP
Control voltage ON
As soon as one of these conditions is not fulfilled, the high-voltage is switched off
immediately. After the fault has been eliminated and acknowledged, the enabling
mechanism can be selected again. An automatic switch on is prevented by the hardware
locking.
Incorrect use!
Risk of injury and damage to the device.
Protective and monitoring equipment must not be removed,
modifi ed or rendered unusable.
Regularly check that they are working perfectly.
If defects are detected on protective and monitoring equipment,
the system must not be operated until these defects are
remedied.
WARNING
Содержание PEA-C4-HiCoat FM
Страница 2: ......
Страница 66: ...66 PEA C4 HiCoat OPERATING MANUAL VERSION 05 2012 ORDER NUMBER DOC 390829 14 4 EC TYPE EXAMINATION CERTIFICATE...
Страница 67: ...67 PEA C4 HiCoat OPERATING MANUAL VERSION 05 2012 ORDER NUMBER DOC 390829...
Страница 68: ...68 PEA C4 HiCoat OPERATING MANUAL VERSION 05 2012 ORDER NUMBER DOC 390829...
Страница 69: ...69 PEA C4 HiCoat OPERATING MANUAL VERSION 05 2012 ORDER NUMBER DOC 390829...
Страница 71: ......