Cleaning and caring for the inverter
29
9
Cleaning and caring for the inverter
a
Caution
Do not use any sharp or hard objects for cleaning since they may
damage the device.
➤
Occasionally clean the device with a damp cloth.
10
Rectifying faults
I
Note
If you have detailed questions on the
specifications
of the invert-
er
please contact WAECO.
Fault
Cause
Remedy
No output voltage
No contact to the battery
Battery voltage less than 11 V
(MSP 162/MSP 352) or 22 V
(MSP 164/MSP 354)
Overheating
Defective fuse (in the inverter
or the vehicle)
Check contact and cable.
Charge the battery (start the
engine).
Switch off power consuming
devices.
Let the inverter cool down
and ensure better ventilation.
Have an electrician change
the fuse.
Warning signal during oper-
ation
The battery voltage is less than
11 V (MSP 162/MSP 352) or
22 V (MSP 164/MSP 354)
Poor contact to the battery
Charge the battery.
Clean the contacts.
Warning sound during oper-
ation below nominal load
Insufficient battery power.
Inadequate cable connection
(cross section too small or poor
contact).
Charge the battery.
Use a cable with a larger
cross section and check
contacts.
The device switches on and
off repeatedly
Excessive constant load
Reduce the load.
The inverter switches off
when the consumer is
switched on
Starting current too high
Compare the device power
with the maximum power of
the inverter.