Troubleshooting
Compressor does not run
Interior temperature too low in control setting 1
Fault
Possible cause
Remedy
U
T
= 0 V
The connection between the battery
and the – electronics is interrupted
Establish a connection
Main switch defective (if installed)
Replace the main switch
Additional supply line fuse has blown
(if installed)
Replace the fuse
U
T
≤
U
ON
Battery voltage is too low
Charge the battery
Start attempt with
U
T
≤
U
OFF
Loose cables
Poor contact (corrosion)
Establish a connection
Battery capacity too low
Replace the battery
Cable cross section too low
Replace the cable
(
h
, page 8)
Start attempt with
U
T
≥
U
ON
Ambient temperature too high
–
Insufficient ventilation and/or cooling
Provide improved
ventilation for the
cooling unit
Condenser is dirty
Clean the condenser
Fan defective (if installed)
Replace the fan
U
T
Voltage between the positive and negative electronic terminals
U
ON
Switch-on voltage of the electronics
U
OFF
Switch-off voltage of the electronics
Fault
Possible cause
Remedy
Compressor runs
constantly
Thermostat sensor has no contact on
the vaporiser
Secure the sensor
Thermostat defective
Change the thermostat
Compressor runs for
a long time
Large quantities have been frozen in
the freezer compartment
–