Installing the cooling unit
ColdMachine
34
6
Installing the cooling unit
6.1
Notes on the cooling container
Permitted cooling area contents
Make sure that maximum cooling area contents specified are not exceeded
for the respective vaporiser type (see the “Technical data” chapter on
page 43).
Minimum insulation
The maximum cooling area contents are based on a minimum insulation
thickness of 35 mm of foam polyurethane with a density of 40 kg/m³. If other
insulating materials are used such as styrofoam, double the wall thickness to
attain the same level of heat insulation.
Installing the vaporiser
The vaporiser must be installed in the cooling container. Observe the
following in the process:
z
Correct installation position (
3
, page 4 up to
0
, page 6)
z
Arrangement in the cooling container as far to the top as possible
z
Install a least 10 mm from the wall.
For cooling units without valve couplings (ready-to install units):
Do not open the refrigerant circuit during installation. You may have
to make the wall openings larger to be able to slide the vaporiser
through them (
a
, page 6). Or alternatively, you create an opening
that allows you to install the cooling lines at the top (
b
, page 6).