EN
97
ASC2500
Service tasks
“R134a to system”
indicates how many grams of refrigerant have been
added to the air conditioning systems using the menu item
“Short selec-
tion”
or
“Free selection”
since the last reset (see date).
“Vacuum time”
indicates how long the vacuum pump has operated
since the last reset (see date).
“Service completed”
displays the amount of service work performed
using the air conditioning service unit since the last reset (see date).
9.4
Calibrating the pressure transducer
I
1. In the basic menu, use the cursor keys
or
to select
“Other
selections”
:
2. Press
ENTER
to confirm.
3. Use the cursor keys
or
to select
“Service”
:
4. Press
ENTER
to confirm.
R134a to system
07/03/14
g.
1200
STOP-EXIT
Vacuum time
07/03/14
min.
79
STOP-EXIT
Service completed:
08/03/14
Number
4
STOP-EXIT
NOTE
The pressure transducer has to be correctly calibrated in order to make
accurate pressure measurements.
Calibration is required:
Every four weeks
If the AirConServiceCenter has been subjected to heavy shaking
Every time the vacuum pump oil is changed
If the display shows implausible pressure readings
Short selection
Free selection
Other selections
ENTER-OK
Int. vessel filling
Flushing
Reset scales.
Service.
Содержание AirConServiceCenter ASC2500
Страница 2: ......
Страница 117: ...ES 117 ASC2500 Seguridad Para manipular refrigerantes lleve gafas de protecci n...
Страница 228: ...RU ASC2500 228 1 2 A I ENTER Short selection 1 2 3 1 2 3 1 233 234 7 A E...
Страница 229: ...RU 229 ASC2500 2 2 1 AirConServiceCenter R 134a AirConServiceCenter WAECO AirConServiceCenter AirConServiceCenter...
Страница 231: ...RU 231 ASC2500 2 3 3 AirConServiceCenter 500 100 10 46...
Страница 233: ...RU 233 ASC2500 AirConServiceCenter 6 AirConServiceCenter 6 1 1 2 3 4 5 6 7 8 9 10 14 12 2 3 4 6 9 15 1 5 11 10 7 13 8...
Страница 234: ...RU AirConServiceCenter ASC2500 234 11 12 13 14 15 6 2 16 500 17 500 18 19 20 20 16 17 18 19...
Страница 240: ...RU ASC2500 240 7 7 1 19 16 17 18 2 19 3 241 19 16 18 17...
Страница 262: ...RU ASC2500 262 5 19 16 17 18 ENTER 6 16 18 17 19 7 STOP 19 16 18 17...
Страница 267: ...RU 267 ASC2500 9 5 1 10 2 D E 3 AirConServiceCenter I 4 G 5 J AirConServiceCenter D D E E G H J I...
Страница 271: ...RU 271 ASC2500 9 8 1 14 K 2 K 9 9 AirConServiceCenter AirConServiceCenter 49 0 25 72 8 79 191 I WAECO K...
Страница 272: ...RU ASC2500 272 1 D 2 L 3 4 5 6 I Other selections Service 1518 ENTER D D L...
Страница 273: ...RU 273 ASC2500 9 10 I 18 6 1 19 18 2 M N 6 19 18 M N...
Страница 274: ...RU ASC2500 274 3 O P 4 N Q 5 9 11 10 11 12 13 AirConServiceCenter O P Q N...
Страница 275: ...RU 275 ASC2500 10 10 1 I 10 2 10 3 AirConServiceCenter M...
Страница 278: ...RU ASC2500 278 Error 02 Error 09 Error 10 Error 11 Error 12...