EN
109
ASC2500
Troubleshooting
The display shows
“Not enough UV. Add!”
This message appears dur-
ing the filling process if there
is not enough UV additive in
the container to finish the
process.
Fill the UV additive container.
The display shows
“Not enough oil. Add!”
Message that appears during
the filling process if there is
not enough fresh oil in the
container to finish the pro-
cess.
Top up the fresh oil container
with a suitable oil type.
The display shows
“Max. filling time
exceeded! Carry on?
”
Message that appears during
the filling process if the set
amount of refrigerant cannot
be filled.
Check that
AirConServiceCenter
connections are not blocked.
The display shows
“External tank empty or
closed valve. Check!
”
Message that appears at the
start or during the filling of
the internal refrigerant con-
tainer if the set refrigerant
quantity cannot be attained.
Check if the external refriger-
ant container still contains
enough refrigerant or if the
valves of the external refrig-
erant container are open.
The display shows
“Change the equipment
drier filter! Go on?
”
This message appears when
you switch on the
AirConServiceCenter.
Change the internal filter as
soon as possible (chapter
“Changing the dryer filter” on
page 95). To skip this, press
ENTER
for 3 seconds.
The display shows
“Change the vacuum pump
oil! Go on?
”
This message appears when
you switch on the
AirConServiceCenter.
Change the vacuum pump oil
as soon as possible (chapter
“Changing the vacuum pump
oil” on page 99). To skip this,
press
ENTER
for 3 seconds.
The display shows
“Printer not in line!
Carry on?
”
Message indicates a printer
fault.
Check if there is paper in the
printer.
Check if the printer is
switched on (yellow LED
must light up constantly).
Check that the cover is
closed properly.
The display shows
“
Error 01”
Refrigerant was added
before draining was com-
pleted.
Repeat the draining proce-
dure; do not interrupt it this
time.
The display shows
“
Error 02”
The air conditioning system
is leaking. There is still refrig-
erant in the air conditioning
system.
Fix the leak.
The display shows
“Error 09”
Low pressure connector not
connected to the flush con-
tainer during flushing.
Connect low pressure hose
to the flush box and open
valve.
Problem
Cause
Remedy
Содержание AirConServiceCenter ASC2500
Страница 2: ......
Страница 117: ...ES 117 ASC2500 Seguridad Para manipular refrigerantes lleve gafas de protecci n...
Страница 228: ...RU ASC2500 228 1 2 A I ENTER Short selection 1 2 3 1 2 3 1 233 234 7 A E...
Страница 229: ...RU 229 ASC2500 2 2 1 AirConServiceCenter R 134a AirConServiceCenter WAECO AirConServiceCenter AirConServiceCenter...
Страница 231: ...RU 231 ASC2500 2 3 3 AirConServiceCenter 500 100 10 46...
Страница 233: ...RU 233 ASC2500 AirConServiceCenter 6 AirConServiceCenter 6 1 1 2 3 4 5 6 7 8 9 10 14 12 2 3 4 6 9 15 1 5 11 10 7 13 8...
Страница 234: ...RU AirConServiceCenter ASC2500 234 11 12 13 14 15 6 2 16 500 17 500 18 19 20 20 16 17 18 19...
Страница 240: ...RU ASC2500 240 7 7 1 19 16 17 18 2 19 3 241 19 16 18 17...
Страница 262: ...RU ASC2500 262 5 19 16 17 18 ENTER 6 16 18 17 19 7 STOP 19 16 18 17...
Страница 267: ...RU 267 ASC2500 9 5 1 10 2 D E 3 AirConServiceCenter I 4 G 5 J AirConServiceCenter D D E E G H J I...
Страница 271: ...RU 271 ASC2500 9 8 1 14 K 2 K 9 9 AirConServiceCenter AirConServiceCenter 49 0 25 72 8 79 191 I WAECO K...
Страница 272: ...RU ASC2500 272 1 D 2 L 3 4 5 6 I Other selections Service 1518 ENTER D D L...
Страница 273: ...RU 273 ASC2500 9 10 I 18 6 1 19 18 2 M N 6 19 18 M N...
Страница 274: ...RU ASC2500 274 3 O P 4 N Q 5 9 11 10 11 12 13 AirConServiceCenter O P Q N...
Страница 275: ...RU 275 ASC2500 10 10 1 I 10 2 10 3 AirConServiceCenter M...
Страница 278: ...RU ASC2500 278 Error 02 Error 09 Error 10 Error 11 Error 12...