Initial start-up
7.9
Filling up the internal refrigerant container
When the AirConServiceCenter is started for the first time, the internal
refrigerant container must be filled from an external refrigerant tank with
at least 5000 g of refrigerant.
I
The current supply quantities are displayed in the standby menu.
There are three different types of refrigerant vessel available:
Refrigerant bottles without rising pipe:
These refrigerant bottles have
one
connection.
When filling the AirConServiceCenter, the connection must be on the
bottom (turn the bottle upside down).
Refrigerant bottles with rising pipe:
These refrigerant bottles have
one
connection.
When filling the AirConServiceCenter, the connection must be at the
top (place the bottle upright).
Refrigerant bottles with rising pipe:
These refrigerant bottles have
two
connections. To top up the
AirConServiceCenter, use the connection marked with
L
(= liquid).
When filling the AirConServiceCenter, the connection must be at the
top (place the bottle upright).
1. In the basic menu, use the cursor keys
or
to select
“Other
selections”
:
2. Press
ENTER
to confirm.
3. Use the cursor keys
or
to select
“Int. vessel filling”
:
4. Press
ENTER
to confirm.
NOTE
Note the instructions on the refrigerant vessels.
Short selection
Free selection
Other selections
ENTER-OK
Int. vessel filling
Flushing
Reset scales.
Service
Содержание AirConServiceCenter ASC 3500 G LE
Страница 2: ......
Страница 242: ...RU ASC2500G ASC3500G 242 1 2 A I ENTER Short selection 1 2 3 1 2 3 1 248 249 8 A E...
Страница 245: ...RU 245 ASC2500G ASC3500G 2 2 AirConServiceCenter 230 50 2 3...
Страница 249: ...RU 249 ASC2500G ASC3500G AirConServiceCenter 11 12 13 14 15 16 USB 17 6 2 18 500 19 500 20 21 22 22 20 19 18 21...
Страница 255: ...RU 255 ASC2500G ASC3500G 7 7 1 21 18 19 20 2 21 3 256 20 19 18 21...
Страница 263: ...RU 263 ASC2500G ASC3500G I 8 2 2 1 STOP ENTER USER CODE WRONG CODE Max Mustermann...
Страница 280: ...RU ASC2500G ASC3500G 280 5 21 18 19 20 ENTER 6 18 20 19 21 7 STOP 20 19 18 21...
Страница 285: ...RU 285 ASC2500G ASC3500G 9 5 1 10 2 D E 3 AirConServiceCenter I 4 G AirConServiceCenter D E D E G H J I...
Страница 290: ...RU ASC2500G ASC3500G 290 9 9 USB USB I AirConServiceCenter 1 USB 2 USB USB 16 USB FAT32 16...
Страница 292: ...RU ASC2500G ASC3500G 292 9 10 I 20 6 1 21 20 2 M N 6 20 21 M N...
Страница 293: ...RU 293 ASC2500G ASC3500G 3 O P 4 N Q 5 9 11 11 12 13 14 AirConServiceCenter P O Q N...
Страница 294: ...RU ASC2500G ASC3500G 294 10 10 1 I 10 2 10 3 AirConServiceCenter M...
Страница 297: ...RU 297 ASC2500G ASC3500G Error 01 Error 02 Error 03 Error 04 Error 09 Error 10 Error 12 10 C...
Страница 298: ...RU ASC2500G ASC3500G 298 Error 52 USB USB USB FAT32 Error 60 Error 61...