EN
103
ASC2500G/ASC3500G
Service tasks
9.4
Calibrating the pressure transducer
I
1. In the basic menu, use the cursor keys
or
to select
“Other
selections”
:
2. Press
ENTER
to confirm.
3. Use the cursor keys
or
to select
“Service”
:
4. Press
ENTER
to confirm.
5. Enter the password
“2224”
.
6. Confirm
“Pressure transducer”
by pressing
ENTER
.
7. Then follow the instructions in the display.
– Unscrew the service couplings (
13
) and (
14
) from the service
hoses (
11
) and (
12
).
– Use the keypad (
8
) to enter the current local atmospheric pressure
and press
ENTER
to confirm.
I
8. When calibration has been completed, press
ENTER
to exit the
menu.
9. Press
STOP
twice to access the standby menu.
10. Screw the service couplings (
13
) and (
14
) hand-tight onto the service
hoses (
11
) and (
12
), taking care not to mix up the red and blue mark-
ings on the couplings and hoses.
NOTE
The pressure transducer has to be correctly calibrated in order to make
accurate pressure measurements.
Calibration is required:
Every four weeks
If the AirConServiceCenter has been subjected to heavy shaking
Every time the vacuum pump oil is changed
If the display shows implausible pressure readings
Short selection
Free selection
Other selections
ENTER-OK
Int. vessel filling
Flushing
Reset scales.
Service.
NOTE
You can look up the current atmospheric pressure for your region on the
Internet, for example at http://www.meteo24.de/wetter/ under “Luft-
druck” (air pressure).
Содержание AirConServiceCenter ASC 3500 G LE
Страница 2: ......
Страница 242: ...RU ASC2500G ASC3500G 242 1 2 A I ENTER Short selection 1 2 3 1 2 3 1 248 249 8 A E...
Страница 245: ...RU 245 ASC2500G ASC3500G 2 2 AirConServiceCenter 230 50 2 3...
Страница 249: ...RU 249 ASC2500G ASC3500G AirConServiceCenter 11 12 13 14 15 16 USB 17 6 2 18 500 19 500 20 21 22 22 20 19 18 21...
Страница 255: ...RU 255 ASC2500G ASC3500G 7 7 1 21 18 19 20 2 21 3 256 20 19 18 21...
Страница 263: ...RU 263 ASC2500G ASC3500G I 8 2 2 1 STOP ENTER USER CODE WRONG CODE Max Mustermann...
Страница 280: ...RU ASC2500G ASC3500G 280 5 21 18 19 20 ENTER 6 18 20 19 21 7 STOP 20 19 18 21...
Страница 285: ...RU 285 ASC2500G ASC3500G 9 5 1 10 2 D E 3 AirConServiceCenter I 4 G AirConServiceCenter D E D E G H J I...
Страница 290: ...RU ASC2500G ASC3500G 290 9 9 USB USB I AirConServiceCenter 1 USB 2 USB USB 16 USB FAT32 16...
Страница 292: ...RU ASC2500G ASC3500G 292 9 10 I 20 6 1 21 20 2 M N 6 20 21 M N...
Страница 293: ...RU 293 ASC2500G ASC3500G 3 O P 4 N Q 5 9 11 11 12 13 14 AirConServiceCenter P O Q N...
Страница 294: ...RU ASC2500G ASC3500G 294 10 10 1 I 10 2 10 3 AirConServiceCenter M...
Страница 297: ...RU 297 ASC2500G ASC3500G Error 01 Error 02 Error 03 Error 04 Error 09 Error 10 Error 12 10 C...
Страница 298: ...RU ASC2500G ASC3500G 298 Error 52 USB USB USB FAT32 Error 60 Error 61...