EN
Troubleshooting
ASC 5300 G
124
The display shows
“Not enough UV.
Add!”
This message appears dur-
ing the filling process if there
is not enough UV additive in
the container to finish the
process.
Fill the UV additive container.
The display shows
“Not enough oil.
Add!”
Message that appears during
the filling process if there is
not enough fresh oil in the
container to finish the pro-
cess.
Top up the fresh oil container
with a suitable oil type.
The display shows
“Max. filling time
exceeded!
Carry on?”
Message that appears during
the filling process if the set
amount of refrigerant cannot
be filled.
Check that
AirConServiceCenter con-
nections are not blocked.
The display shows
“External tank empty or
closed valve.
Check!”
Message that appears at the
start or during the filling of
the internal refrigerant con-
tainer if the set refrigerant
quantity cannot be attained.
Check if the external refriger-
ant container still contains
enough refrigerant or if the
valves of the external refrig-
erant container are open.
The display shows
“Change the equipment
drier filter!
Go on?”
This message appears when
you switch on the
AirConServiceCenter.
Change the internal filter as
soon as possible (see chap-
ter “Changing the dryer filter”
on page 110).
To continue press
ENTER
.
The display shows
“Change the vacuum pump
oil!
Go on?”
This message appears when
you switch on the
AirConServiceCenter.
Change the vacuum pump oil
as soon as possible (see
chapter “Changing the vac-
uum pump oil” on page 115).
To continue press
ENTER
.
The display shows
“Printer not in line!
Carry on?”
Message indicates a printer
fault.
Check if there is paper in the
printer.
Check if the printer is
switched on (yellow LED
must light up constantly).
Check that the cover is
closed properly.
The display shows
“Error 01”
Refrigerant was added
before draining was com-
pleted.
Repeat the draining proce-
dure; do not interrupt it this
time.
The display shows
“Error 02”
The air conditioning system
is leaking. There is still refrig-
erant in the air conditioning
system.
Fix the leak.
The display shows
“Error 09”
Low pressure connector not
connected to the flush con-
tainer during flushing.
Connect low pressure hose
to the flush box and open
valve.
Problem
Cause
Remedy
ASC5300G_OPM_DE-EN-ES-FR-RU.book Seite 124 Freitag, 26. Juni 2020 5:42 17
Содержание AirCon Service Center ASC 5300 G
Страница 66: ...DE Technische Daten ASC 5300 G 66 ASC5300G_OPM_DE EN ES FR RU book Seite 66 Freitag 26 Juni 2020 5 42 17...
Страница 132: ...EN Technical data ASC 5300 G 132 ASC5300G_OPM_DE EN ES FR RU book Seite 132 Freitag 26 Juni 2020 5 42 17...
Страница 198: ...ES Datos t cnicos ASC 5300 G 198 ASC5300G_OPM_DE EN ES FR RU book Seite 198 Freitag 26 Juni 2020 5 42 17...
Страница 267: ...FR 267 ASC 5300 G Caract ristiques techniques ASC5300G_OPM_DE EN ES FR RU book Seite 267 Freitag 26 Juni 2020 5 42 17...
Страница 321: ...RU 321 ASC 5300 G 9 9 1 14 K 2 K K ASC5300G_OPM_DE EN ES FR RU book Seite 321 Freitag 26 Juni 2020 5 42 17...
Страница 334: ...RU ASC 5300 G 334 13 2 ASC5300G_OPM_DE EN ES FR RU book Seite 334 Freitag 26 Juni 2020 5 42 17...
Страница 335: ...RU 335 ASC 5300 G ASC5300G_OPM_DE EN ES FR RU book Seite 335 Freitag 26 Juni 2020 5 42 17...