16.6 Extension cable
Only use permitted extension cables, see chapter
Safety
.
Refer to the following table for the required cross-section area of the
extension cable:
Note:
Refer to the nameplate or the chapter
Technical data
(via the item
number) for the type designation and voltage rating of your machine.
Example
You utilize an M1000/120 and want to use an extension cable with a length of
25 m.
The machine has an input voltage of 120 V.
According to the table, the extension cable must feature a cross-section area of
2.5 mm
2
.
WARNING
Electrical voltage.
Injuries from electrocution.
X
Check power cable and extension cable for signs of damage.
X
Only use extension cables for which grounded conductors are connected to
the plug and the coupling (only for machines of class rating I, see chapter
Technical Data
).
Machine
Voltage
[V]
Extension
[m]
Cross-section
area of cable
[mm
2
]
M1000
120 1~
< 31
1,5
< 52
2,5
< 82
4,0
M2000
M3000
120 1~
< 21
1,5
< 35
2,5
< 55
4,0