Operation
Auto Mode (Auto Start/Stop) (if equipped) 7.13
71
[en-US] | 02/2023 | 5100065071 | LTV 4L/6L | Operator’s Manual
Ref.
Description
Ref.
Description
1
Next section
2
Previous section
3
Previous parameter
4
Edit or save parameter
5
Next parameter
— —
Editing a parameter
Notes:
• Use the Deep Sea computer software for more comprehensive module
configuration.
• If a PIN code is required, contact the generator supplier for the PIN code.
If the PIN code is lost or forgotten, return the controller to the Deep Sea
factory to reset the code. For security purposes, the PIN code entry auto-
matically clears when the editor is exited (manually or automatically).
1.
To enter the editor mode, press and hold the Stop
(3)
and Auto
(4)
but-
tons simultaneously.
2.
Press the up
(1)
and down
(2)
arrows to select the Operator Editor (hu-
man icon) or Configuration Editor (wrench icon). The selected editor
flashes.
3.
Press Auto to enter the selected editor.
Note:
If a PIN code has been set for the Configuration Editor, the PIN
request appears.
4.
Press the up and down arrows to adjust first digit to the correct value.
5.
Press the Start button
(5)
when the first digit is correctly entered. The
digit changes to # for security purposes.
6.
Enter each of the digits of the PIN code. Press Stop to move back to
adjust one of the previous digits.
7.
After entering the last digit, press Auto to validate the PIN code. If the
number is not correct, the editor is exited.
8.
Once in the selected editor, press the up and down arrows to cycle
through sections in increments of 100. Press Stop or Start to cycle
through the parameters in increments of 1. The table below lists the pa-
rameters needed to configure a schedule.
Note:
Parameter numbers and entry value numbers match what is in
the controller. However, descriptions in these tables may have been
modified to help clarify the parameter function.
9.
To select a parameter to edit, press Auto. The parameter value flashes.
10.
Press Stop or Start to adjust the value to the required setting.
11.
Press Auto to the save the current value. The value stops flashing.
Note:
For security purposes, the editor automatically exits after 5 min-
utes of inactivity.
12.
To save and exit the editor, press and hold Auto. To exit without sav-
ing, press and hold Stop.
Note:
In the table below, the bold entry choices are required for Auto Mode.
7
Содержание LTV 4L
Страница 4: ...This page is intentionally left blank...
Страница 104: ...Index 104 Operator s Manual LTV 4L 6L 5100065071 02 2023 en US...
Страница 105: ......