Operation
G 50/G 70/G 85
wc_tx000483gb.fm
44
3.29 Remote/Transfer Switch
See Graphic: wc_gr002611
When the generator is used as a standby power supply, it must be
equipped with a device which isolates it from the utility’s distribution
system.
Failure to isolate the generator from the utility’s electrical
distribution system could cause output from the generator to
backfeed into the utility lines and cause injury or death to utility
workers!
The same is true if using the generator as a backup to some other type
of power supply system.
A transfer switch is designed to transfer electrical loads from the
normal power source (utility) to the emergency power source
(generator) when normal voltage falls below a prescribed level.
The transfer switch automatically returns the load back to the normal
source when power is restored back to operating levels.
Installation of a transfer switch or other type of remote starting device
is the responsibility of the generator user. Installation of such devices
must be performed by a qualified electrician following all directions
supplied by the manufacturer of the switch. If attaching generator to a
power supply normally serviced by a utility company, notify the utility
company and check local and state regulations. Familiarize yourself
with all instructions and warning labels supplied with the switch.
The bond bar
(t)
, connecting the neutral and ground lugs, may need to
be removed for standby power applications. Check with NEC and local
regulations for compliance requirements.
When using the generator as a standby or substitute power supply,
make sure the voltage and phase rotation of the line connections
match those of the utility lines, or of any other power source normally
used.
Failure to match phase rotation and voltage may cause
equipment connected to the generator to operate incorrectly!
This could create unsafe operating conditions.
Lethal voltage is always present in the transfer switch once it has been
properly installed!
DANGER
WARNING
DANGER
Содержание G70
Страница 2: ......
Страница 14: ...Safety Information G 50 G 70 G 85 wc_si000158gb fm 14 2 6 Label Location...
Страница 15: ...G 50 G 70 G 85 Safety Information wc_si000158gb fm 15...
Страница 24: ...Operation G 50 G 70 G 85 wc_tx000483gb fm 24 3 Operation 3 1 Control Panels...
Страница 46: ...Operation G 50 G 70 G 85 wc_tx000483gb fm 46 w c _ g r 0 0 0 5 1 0 a d c b...
Страница 57: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 57...
Страница 59: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 59...
Страница 65: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 65 G 50 G 70 Engine Wiring...
Страница 67: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 67 G 50 G 70 Engine Wiring...
Страница 69: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 69 G 50 G 70 Engine Wiring...
Страница 73: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 73...
Страница 81: ...Mobile Generators Factory Installed Options wc_tx000380gb fm 81 Notes...
Страница 90: ...Technical Data G50 G 70 G 85 90 6 4 Dimensions mm inches...
Страница 91: ......