Operation
G 50/G 70/G 85
wc_tx000483gb.fm
38
3.20 Manual Start-up
See Graphic: wc_gr001682, wc_gr001677, wc_gr002611
Before starting the generator set, thoroughly review the pre-start-up
checklist in the previous section. Proceed with generator start-up only
after checking each item in that section.
Thoroughly read and make sure you understand the engine Operator’s
Manual supplied with the generator. Follow the steps below and the
illustration on the opposite page in the order listed.
When using the generator as a standby or substitute power supply,
make sure the voltage and phase rotation of the line connections
match those of the utility lines or of any other power source normally
used.
Failure to match phase rotation and voltage may cause
equipment connected to the generator to operate incorrectly!
This could create unsafe operating conditions.
3.20.1
Check position of Voltage Selector Switch and make sure it is set for
the desired voltage output. Lock the switch in place.
3.20.2
Make sure the Engine Start Switch
(f)
is in the off “O” position.
3.20.3
Turn main line circuit breaker
(a)
and convenience receptacle circuit
breakers to off “O”. This will disconnect all loads from the generator.
3.20.4
Move Engine Start Switch
(f)
to “REMOTE START” to check operation
of engine control module. The LCD panel should momentarily display
“SYSTEM OK”
followed by
“UNIT IN AUTO”
and engine information.
Check fuel level and battery values.
Note:
The amber Warning Light
(d)
will come on if the fuel level is
below 25%, or engine temperature is below 70°F. This will not prevent
the engine from starting.
3.20.5
Press in the Emergency Stop Button
(p)
. The LCD panel should read
“EMERGENCY STOP”
. Release the stop button after verifying the
display and return the Engine Start Switch to off “O”.
3.20.6
Start engine by moving the Engine Start Switch to the “START/RUN”
position.
After displaying
“GLOW PLUG ON”
sequence, the LCD display will
read
“STARTING ENGINE”
as the engine begins its crank cycle. The
normal cycle is for the engine to crank for 15 seconds, then rest for 10
seconds. This cycle will repeat three (3) times. If the engine does not
start within this time, the Engine Control Module will shut down the
engine and “
FAULT OVERCRANK”
will be displayed on the LCD
panel. To repeat crank cycle, return start switch to off “O” to reset
Engine Control Module. Allow starter motor to cool between start-up
attempts.
WARNING
Содержание G70
Страница 2: ......
Страница 14: ...Safety Information G 50 G 70 G 85 wc_si000158gb fm 14 2 6 Label Location...
Страница 15: ...G 50 G 70 G 85 Safety Information wc_si000158gb fm 15...
Страница 24: ...Operation G 50 G 70 G 85 wc_tx000483gb fm 24 3 Operation 3 1 Control Panels...
Страница 46: ...Operation G 50 G 70 G 85 wc_tx000483gb fm 46 w c _ g r 0 0 0 5 1 0 a d c b...
Страница 57: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 57...
Страница 59: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 59...
Страница 65: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 65 G 50 G 70 Engine Wiring...
Страница 67: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 67 G 50 G 70 Engine Wiring...
Страница 69: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 69 G 50 G 70 Engine Wiring...
Страница 73: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 73...
Страница 81: ...Mobile Generators Factory Installed Options wc_tx000380gb fm 81 Notes...
Страница 90: ...Technical Data G50 G 70 G 85 90 6 4 Dimensions mm inches...
Страница 91: ......