![Wacker Neuson G70 Скачать руководство пользователя страница 29](http://html1.mh-extra.com/html/wacker-neuson/g70/g70_operators-manual_3129214029.webp)
G 50/G 70/G 85
Operation
wc_tx000483gb.fm
29
3.5
Current Overload Fault
Along with engine functions the ECM continuously monitors the current
load in each phase. The values for current overload are programmed
into the ECM at the factory and are different for each generator size.
When an overload condition is sensed in any leg, the engine will shut
down and the LCD panel will display the fault condition shown above.
Before restarting the generator, the cause of the overload should be
determined and eliminated. Review all loads attached to the generator
and make sure they do not exceed the power rating of the unit.
3.6
Application
Heavy-duty, compact, sound-attenuated generators designed to
provide single and three-phase power for construction, commercial,
and industrial applications where reliable power is needed.
NOTICE
:
Do not exceed the power output of the generator. Damage
to tools or generator will occur. Refer to
Technical Data
.
When using the generator as a standby or substitute power supply,
make sure the voltage and phase rotation of the line connections
match those of the utility lines or of any other power source normally
used.
Failure to match phase rotation and voltage may cause
equipment connected to the generator to operate incorrectly!
This could create unsafe operating conditions.
NOTICE
:
DO NOT exceed the rated current limit of any receptacle.
Normal operating pressure is between 40–80
psi. If oil pressure drops below 15 psi, the
engine will automatically shut down.
For machines with the Low-Coolant Shutdown
Option only. This fault will be displayed when
the ECM has picked up a signal from the sen-
sor that a low-coolant level exists. During such
a condition, the ECM shuts the engine down.
LOW OIL LEVEL
FAULT
LOW WATER LEVEL
FAULT
OVERLOAD
Содержание G70
Страница 2: ......
Страница 14: ...Safety Information G 50 G 70 G 85 wc_si000158gb fm 14 2 6 Label Location...
Страница 15: ...G 50 G 70 G 85 Safety Information wc_si000158gb fm 15...
Страница 24: ...Operation G 50 G 70 G 85 wc_tx000483gb fm 24 3 Operation 3 1 Control Panels...
Страница 46: ...Operation G 50 G 70 G 85 wc_tx000483gb fm 46 w c _ g r 0 0 0 5 1 0 a d c b...
Страница 57: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 57...
Страница 59: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 59...
Страница 65: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 65 G 50 G 70 Engine Wiring...
Страница 67: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 67 G 50 G 70 Engine Wiring...
Страница 69: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 69 G 50 G 70 Engine Wiring...
Страница 73: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 73...
Страница 81: ...Mobile Generators Factory Installed Options wc_tx000380gb fm 81 Notes...
Страница 90: ...Technical Data G50 G 70 G 85 90 6 4 Dimensions mm inches...
Страница 91: ......