EHB 11
Technical data
47
12.5
Extension cable
A permitted extension cable must fulfill the following criteria:
The extension cable must be undamaged.
The extension cable has to be connected correctly on plug and bushing.
The extension cable has to be suitable for use at construction sites: Average
rubber hose H05RN-F or better – WACKER recommends H07RN-F or a
country-specific equivalent design.
The extension cable must have been checked by a qualified electrician.
The required cross-section area of a designated extension has been taken
from the table below.
Note:
Refer to the nameplate or the chapter
Technical data
(via the item
number) for the type designation and voltage rating of your machine.
Voltage
[V]
Extension
[m]
Cross-section
area of cable
[mm
2
]
110–130
< 8
1.5
< 13
2.5
< 20
4.0
< 30
6.0
220–240
< 27
1.5
< 44
2.5
< 70
4.0
< 105
6.0