Wachendorff DA9602 Скачать руководство пользователя страница 7

 Operating manual 

 

 

 

- 7 - 

Two different functions can be assigned to F1 and F2 keys. The function to be executed, Primary or 
Secondary, is determined by the amount of time the function key is being pressed. If the function 
key is pressed for less then 1 second the Primary function is executed. 
If the key is pressed for more than 3 seconds then the Secondary function is executed. 
The combination of the keys F1 and F2 pressed simultaneously can also execute a Special 
Function. All Special Functions are available to the operator as follows: 

F1_1

:  

F1 Key, Primary Function. 

F1_2

:  

F1 Key, Secondary Function. 

F2_1

:  

F2 Key, Primary Function. 

F2_2

:  

F2 Key, Secondary Function. 

F12_1

:  

F1+F2 Keys, Primary Function. 

F12_2

:  

F1+F2 Keys, Secondary Function. 

The totalization alarm functions 



 

and 



 

allow the user to notify when a total value is reached. 

The alarm defined as Totalization Minimum Value Alarm 



) is set when the totalization value 

goes below the configured setpoint. 
The alarm defined as Totalization Maximum Value Alarm (



) is set when the totalization value 

goes above the configured setpoint. 
As the totalization value can indicate up to 99999 99999 (or -9999 99999) the set point values 
behave the same way. If the adjusted SP goes above 99999 (or below -9999) the second SP part is 
displayed allowing the operator to see values up to 99999 99999 (or -9999 99999). 
The flags HIGH and LOW identify if the part being displayed is the SP most significant part (HIGH) 
or the least significant part (LOW). 
The totalization alarm (SP) is defined through the values SPA1 and SPA2. This two parameters 
behave different from other parameters. The Back key allows the operator to change the SP 
decimal digit to be set. 

4.11 Overflow 

alarm 

This alarm function is set when the totalized value surpasses 9999999999, which is the maximum 
indication value. 

4.12 Minimum 

and 

maximum 

The indicator is continuously storing the extreme input indication measurements, or the minimum 
and maximum values. These values can be displayed at any time by the operator by pressing the 
keys F1 and F2. Notice that the function Keys should be set to 



 

and 



To reset the maximum and minimum values and start another another monitoring cycle, just 
execute the function 



, which can be assigned to the keys F1 and F2. When the indicator is 

powered off this information is not stored. 

4.13  24 VDC auxiliary voltage source 

The standard version of the DA9602 provides an auxiliary power supply (24 VDC) for exciting field 
transmitters (terminal 13 on the rear panel). 

4.14 Interface 

USB-Port (virtual COM-Port) to program the digital display. 
 
 

5. Installation 

5.1  

Mechanical installation 

The indicator is meant for panel mounting. The sequence of steps is:  

 

Prepare a cut out of 93.0 by 45.5 mm on the panel 

 

Remove the mounting clamp from the indicator 

 

Insert the indicator into the cut out from the front side of the panel 

 

Place the clamp on the indicator again, pressing until firm grip to the panel  

Содержание DA9602

Страница 1: ...ndorff Prozesstechnik GmbH Co KG Industriestra e 7 D 65366 Geisenheim Tel 49 6722 9965 20 Fax 78 All Information without warranty errors and changes reserved Universal display DA9602 Operating manual...

Страница 2: ...on 6 4 10 F1 and F2 function keys 6 4 11 Overflow alarm 7 4 12 Minimum and maximum 7 4 13 24 VDC auxiliary voltage source 7 4 14 Interface 7 5 Installation 7 5 1 Mechanically installation 7 5 2 Electr...

Страница 3: ...vent dangerous situations on machinery and installations Machinery and intallations must be designed that fault conditions can not lead to harmful situations to operating personnel e g by independent...

Страница 4: ...mocouple K Range 150 C to 1370 C 238 F to 2498 F Thermocouple T Range 160 C to 400 C 256 F to 752 F Thermocouple N Range 270 C to 1300 C 454 F to 2372 F Thermocouple R Range 50 C to 1760 C 58 F to 320...

Страница 5: ...oint defined by ALrF SPA1 using alarm 1 as an example ALrF PV ALrF SPA1 ALrF PV ALrF SPA1 SPA1 positive SPA1 negative Alarm of the Maximum Differential Value It triggers when the value of the PV is ab...

Страница 6: ...ory and can also be presented at the indicator display by choosing TOTAL screen which is identified by the symbol TOT This symbol is always presented when the TOTAL is being presented The TOTAL value...

Страница 7: ...W identify if the part being displayed is the SP most significant part HIGH or the least significant part LOW The totalization alarm SP is defined through the values SPA1 and SPA2 This two parameters...

Страница 8: ...e 5 3 Recommendations for the installation To minimize the pick up of electrical noise the low voltage DC connections and the sensor input wiring should be routed away from high current power conducto...

Страница 9: ...cording to the desired behavior The user shall understand the importance of each parameter and determine a valid condition or a valid value for each one of them The configuration parameters are groupe...

Страница 10: ...SP decimal point SetPoint Alarm Alarm SP Value that defines the point of activation of the alarm outputs For the alarms programmed with the functions of the type Band and Differential these parameter...

Страница 11: ...indication range when the input types of 0 20 mA 4 20 mA 0 50 mV 0 5 V and 0 10 V are used Defines the function to be executed by F1 and F2 keys No associated function Executes Batch Function Addition...

Страница 12: ...p the Level of Protection See Table 03 Frequency Frequency of the local electrical network Serial number 4 most significant digits Serial number 4 least significant digits 8 6 Password protection The...

Страница 13: ...in the event of it being forgotten The Master Password doesn t grant access to all parameters only to the Password Change parameter After defining the new password the protected parameters may be acce...

Страница 14: ...0 mV 10 M 0 to 5 V 0 to10 V 500 k 4 to 20 mA 100 Measuring of the Pt100 3 wire type 0 00385 with compensation of the cable length max 50 meters excitation current of 0 170 mA OUTPUT Output ALARM1 Rela...

Страница 15: ...nical content within this document can be modified without notice The content of this document is content of a recurring audit In losses due to fire earthquake interventions by third or other accident...

Отзывы: