Wachendorff DA9602 Скачать руководство пользователя страница 14

 Operating manual 

 

 

 

- 14 - 

9. Specifications 

 

DIMENSIONS: 

W 96 mm x H 48 mm x D 35 mm 

Panel cut out 

93,0 mm x 45,5 mm 

Approximate weight: 

110 g 

POWER SUPPLY: 

100 VAC to 240 VAC (±10 %), 50/60 Hz 

 

 

100 VDC to 240 VDC (±10 %) 

 

Maximum consumption 

6 VA 

 

ENVIRONMENTAL CONDITIONS: 

Operation Temperature: 

0 °C to50 ºC 

Relative Humidity: 

80 % @ 30 ºC 

For temperatures above 30 ºC, reduce 3 % per ºC 
Indoor use; Installation Category II, Pollution Degree 2; altitude < 2000 meters 

 

INPUT: According 

to 

Table 01 

on page 4 

Internal Resolution: 

65.535 levels (16 bits) 

Display Resolution: 

32.000 levels (from -1.999 to 30.000) 

Input reading rate: 

up to 55 per second 

Precision: Thermocouples 

J

K

,

E

: 0,25 % of the span 

1 ºC 

 Thermocouples 

N

R

,

B

: 0,25 % of the span 

3 ºC 

     

Pt100 (RTD): 0,2 % of the span

 

 

4 to 20 mA, 0 to 50 mV, 0 to 5/10 V: 0.2 % of the span 

Input impedance: 

Pt100, T/C, 0 to 50 mV: > 10 M

 

     

0 to 5 V, 0 to10 V: > 500 k

 

    

4 to 20 mA: 100 

 

Measuring of the Pt100:                   3  wire  type,  (

=0.00385), with compensation of the cable 

length, max 50 meters, excitation current of 0.170 mA.  

 
 

OUTPUT: 

Output ALARM1: 

Relay SPST; 240 VAC / 30 VDC / 1.5 A  

Output ALARM2: 

Relay SPST; 240 VAC / 30 VDC / 1,5 A 

24 VDC source: 

24 VDC (±15 %) / 50 mA max. 

CASE: 

Polycarbonat (PC) UL94 V-2

 

BACK PANEL: 

ABS+PC UL94 V-0 

CONNECTIONS (WIRING):

  

Plug-in block terminals, 5 mm pitch

 

STARTS OPERATION AFTER 3 SECONDS CONNECTED TO THE POWER SUPPLY. 

10.  Error messages, default and calibration 

10.1  Error messages  

Connection errors and inadequate programming are the most common errors found during the 
controller operation. A final revision may avoid loss of time and damages. 
The controller displays some messages to help the user identify problems. 

  

MESSAGE 

DESCRIPTION OF THE PROBLEM 



Open input. No sensor or signal.   




Connection and/or configuration errors. 
Check the wiring and the configuration. 

Other error messages may indicate hardware problems requiring maintenance service. 

 

Содержание DA9602

Страница 1: ...ndorff Prozesstechnik GmbH Co KG Industriestra e 7 D 65366 Geisenheim Tel 49 6722 9965 20 Fax 78 All Information without warranty errors and changes reserved Universal display DA9602 Operating manual...

Страница 2: ...on 6 4 10 F1 and F2 function keys 6 4 11 Overflow alarm 7 4 12 Minimum and maximum 7 4 13 24 VDC auxiliary voltage source 7 4 14 Interface 7 5 Installation 7 5 1 Mechanically installation 7 5 2 Electr...

Страница 3: ...vent dangerous situations on machinery and installations Machinery and intallations must be designed that fault conditions can not lead to harmful situations to operating personnel e g by independent...

Страница 4: ...mocouple K Range 150 C to 1370 C 238 F to 2498 F Thermocouple T Range 160 C to 400 C 256 F to 752 F Thermocouple N Range 270 C to 1300 C 454 F to 2372 F Thermocouple R Range 50 C to 1760 C 58 F to 320...

Страница 5: ...oint defined by ALrF SPA1 using alarm 1 as an example ALrF PV ALrF SPA1 ALrF PV ALrF SPA1 SPA1 positive SPA1 negative Alarm of the Maximum Differential Value It triggers when the value of the PV is ab...

Страница 6: ...ory and can also be presented at the indicator display by choosing TOTAL screen which is identified by the symbol TOT This symbol is always presented when the TOTAL is being presented The TOTAL value...

Страница 7: ...W identify if the part being displayed is the SP most significant part HIGH or the least significant part LOW The totalization alarm SP is defined through the values SPA1 and SPA2 This two parameters...

Страница 8: ...e 5 3 Recommendations for the installation To minimize the pick up of electrical noise the low voltage DC connections and the sensor input wiring should be routed away from high current power conducto...

Страница 9: ...cording to the desired behavior The user shall understand the importance of each parameter and determine a valid condition or a valid value for each one of them The configuration parameters are groupe...

Страница 10: ...SP decimal point SetPoint Alarm Alarm SP Value that defines the point of activation of the alarm outputs For the alarms programmed with the functions of the type Band and Differential these parameter...

Страница 11: ...indication range when the input types of 0 20 mA 4 20 mA 0 50 mV 0 5 V and 0 10 V are used Defines the function to be executed by F1 and F2 keys No associated function Executes Batch Function Addition...

Страница 12: ...p the Level of Protection See Table 03 Frequency Frequency of the local electrical network Serial number 4 most significant digits Serial number 4 least significant digits 8 6 Password protection The...

Страница 13: ...in the event of it being forgotten The Master Password doesn t grant access to all parameters only to the Password Change parameter After defining the new password the protected parameters may be acce...

Страница 14: ...0 mV 10 M 0 to 5 V 0 to10 V 500 k 4 to 20 mA 100 Measuring of the Pt100 3 wire type 0 00385 with compensation of the cable length max 50 meters excitation current of 0 170 mA OUTPUT Output ALARM1 Rela...

Страница 15: ...nical content within this document can be modified without notice The content of this document is content of a recurring audit In losses due to fire earthquake interventions by third or other accident...

Отзывы: