12 

 

3.2.2 Cable requirements  

Before performing the installation, make sure that your setup fulfills the following list of requirements: 

 

All cables and leads must comply with the local and national regulations. 

 

Cable dimensions for PG9 connectors should be within the range of 3-8mm 

 

Cables meet the dimension requirements given in the Table 5. 

 

Copper wires are recommended. 

 

Modbus cable can be 6-wire unshielded, 30 AWG/0,066 m

2

 or similar. 

 

Control wires and cables 

Minimal Conductor 

Dimension 

Maximum Conductor 

Dimension 

Cable dimension 

Solid wires 

0.08 mm

2

 

1.5 mm

2

 

3-8 mm 

Multi-core wires 

0.14 mm

2

 

1.0 mm

2

 

3-8 mm 

Power leads and cables 

Solid wires 

0.2 mm

2

 

4.0 mm

2

 

3-8 mm 

Multi-core wires 

0.2 mm

2

 

2.5 mm

2

 

3-8 mm 

Table 5 Cable and wires dimension requirements 

3.3 Elements of the controller panel 

3.3.1 Test button 

The driver is provided with a test function in the form of a built-in test push-button. The test button is located inside 
the drive in the upper right corner and must be operated with the drive open. The test button has different functions, 
depending on how long the button is pressed in: 

1.  Short  press  <  1sec.:  The  drive  will  enter  test  mode  and  stay  in  test  mode  until  the  button  is  pressed  again. 
The  rotor  will  start  rotating  in  a  sequence  from  0–100  rpm  according  to  the  selected  ramp-up  time  and  remain 
at 100 rpm. Pressing the button a second time will cause the drive to leave test mode and stop the rotor according to 
the selected ramp-down time. 

2. Pressing and holding the button will cause the  drive to enter test mode where it will remain until the button is 
released. The signal to the rotor will override to 100 rpm according to the selected ramp-up time. 

Please  note,  that  when  pressing  the  test  button  for  more  than  20  sec.  the  calibration  function  off  the  internal 
rotorguard may be triggered. 

The test button also works when Modbus control is activated. 

3.3.2 Dip switch 

The driver is equipped with 4 DIP switches for setting  the stepper motor size (see Table 6) and maximum motor speed 
(Table 7). 

 

Figure 18 DIP switch 

Содержание 7-1-0002-0083

Страница 1: ...version 1 2 01 2022 ENERGY RECOVERY WHEEL MOTOR MANUAL OPERATION AND MAINTANANCE...

Страница 2: ...ERAL SAFETY 3 2 PRODUCT DESCRIPTION TECHNICAL SPECIFICATION 3 3 INSTALLATION 6 3 1 Assembly and installation 6 3 2 Connection and wiring 7 3 2 1 Main voltage and stepper motor wiring 10 3 2 2 Cable re...

Страница 3: ...ruction carefully Follow the connection diagrams to perform successful installation 2 PRODUCT DESCRIPTION TECHNICAL SPECIFICATION Rotary Heat Exchangers may be equipped with three different stepper mo...

Страница 4: ...260 W Weight 2 4 kg 3 5 kg 5 0 kg Sealing grade IP 54 54 54 Operating temperature 40 C to 40 C 40 C to 40 C 40 C to 40 C Storage temperature 40 C to 70 C 40 C to 70 C 40 C to 70 C Dimensions 85 x 85 x...

Страница 5: ...Figure 2 Stepper Motor 4 0 Nm all dimensions are given in mm units Figure 3 Stepper Motor 8 0 Nm all dimensions are given in mm units Figure 4 Dedicated controller all dimensions are given in mm unit...

Страница 6: ...of the exchanger and most importantly the risk of motor damage as well as electric shock due to incorrect connection Warning Incorrect mechanical installation of the motor can be a cause of error aler...

Страница 7: ...n the motor wait at least 5 minutes after disconnecting from the power supply Notes on proper installation Use fuses at power line Check the wires condition before operating Make sure that there are n...

Страница 8: ...represents the cable connection with proper wiring description Figure 9 Extension cable Stepper motors are operated via designated controller connected with the motor by the up mentioned cables Figur...

Страница 9: ...attempt to perform any repairs by your own Manufacturer warranty will not be void until the cover has traces of opening Controller is equipped with spring terminals to make the installation faster Sp...

Страница 10: ...ble of the power supply should be connected on the terminals marked with letters L N and PE see Figure 15 Cables should be inserted via dedicated cable entries glands After the wiring is performed rem...

Страница 11: ...11 Figure 16 Stepper motor connection Figure 17 Controller schematic...

Страница 12: ...s located inside the drive in the upper right corner and must be operated with the drive open The test button has different functions depending on how long the button is pressed in 1 Short press 1sec...

Страница 13: ...3 3 3 LED Indicator The driver is fitted with a LED indicator see Figure 19 The LED diode can be seen with both open and closed cover Figure 19 LED indicator The statuses of the indicator are shown in...

Страница 14: ...Read out the current fault alarm via Modbus Table 13 Purging function activated Test function is activated and stepper motor is receiving control signal for max RPM rotations Hold function is activate...

Страница 15: ...analogue 0 10 V input signal The device is factory set for 0 10 V control after detection of a start signal or speed setpoint via Modbus it will automatically shift temporarily to control via Modbus R...

Страница 16: ...nication between the controller and AHU are unchangeable only the alternative parameters are to be changed Note the settings of the device delivered with the VTS AHU are prepared by the manufacturer f...

Страница 17: ...tuses Adress Function Range Active state 0 Rotorguard Alarm 0 1 1 Alarm 1 V LO Alarm 0 1 1 Alarm 2 V HI Alarm 0 1 1 Alarm 3 I HI Alarm Motor out short 0 1 1 Alarm 4 Temperature High 0 1 1 Warning 8 Ro...

Страница 18: ...le 0 100 1 V 13 Config file variant AA ZZ 2 ASCII characters 14 Config file version 100 32000 0 01 15 MOC SW version 0 0 01 16 Rotor Speed Out 0 40000 0 01 RPM 17 Torque 0 1500 0 01 Nm 17 SW variant 1...

Страница 19: ...DHX Type 0 1 13 Alternative Modbus ID 1 247 1 14 Alternative BaudRate 0 9600 bps 1 19200 bps 2 38400 bps 3 57600 bps 4 115200 bps 15 Alternative Parity 0 None 1 Odd 2 Even 16 Alternative Stop Bits 0 I...

Страница 20: ...oller SPR to work with VTS AHU In order to adapt the brand new RRG controller ordered as a spare part to work with the automation of VTS AHUs you should connect to the RRG controller using a USB RS485...

Отзывы: