Heating Checkout

1.

 

Slide mode switch to HEAT, B terminal will get energized.

2.

 

Press 

key until the set point is higher than room temperature. The star symbol is shown on the display.

The heating equipment is on and terminal W is energized.

3.

 

Press the 

Ñ

 

key

 

until set point is lower than room temperature. The star symbol is removed. The heating

equipment  is off and W terminal is de-energized.

Fan Checkout

1.

 

Slide FAN switch to ON position. The G terminal is energized and the fan should always be running.

2.

 

Slide FAN switch to AUTO position,

q

 

In cooling mode, the fan starts and stops with the cooling equipment.

q

 

In heating mode when setup switch is in the F position, the fan is controlled directly by the heating
equipment and may start a few minutes after the heating equipment turns on. When setup switch is in the
E position, the fan starts and stops with the heating equipment.

Application Note

Attached 1000 ohm, 3 watt resistor is used in certain applications to assure compatibility with power stealing
thermostats where Fan does not come ON during call for Heat or Cool. Note that resistor has to be installed
at the fan terminals and not at thermostat terminals.

To install the Resistor

1.

 

Disconnect power supply.

2.

 

Connect the resistor leads to the terminals
as shown in the drawing.

3.

 

Turn on the system power.

Air Handler Fan Board

1000 Ohm
3Watt
Resistor

Thermostat

C G

G

VTRONIX, LLC 318 Indian Trace #327, Weston, FL 33326

Copyright 

©

 

2002 Vtronix  Document no. 170306-000E Rev.01

Содержание TE86S

Страница 1: ...hermostat Model Mounting System Selection Fan Selection Powering Method Backlight TE86S VERTICAL COOL OFF HEAT ON AUTO Power Stealing No Backlight TE86SB VERTICAL COOL OFF HEAT ON AUTO Power Stealing...

Страница 2: ...d 1 5 Amp continuous 0 02 to 1 5 A continuous 0 02 to 1 5 A continuous 0 02 to 0 5 A continuous TEMPERATURE RATINGS Temperature setting range Ambient temperature range Shipping temperature range 40 to...

Страница 3: ...as indicated will result in poor temperature control NOTE Level thermostat mounting is for appearance only and is not required for proper thermostat operation Mounting Thermostat Take out the back pl...

Страница 4: ...s used may result in the overheating of the electric heater elements due to improper fan operation The set up switch is an internal switch E F located near the wiring terminals It is used to select pr...

Страница 5: ...following steps to change each of the settings Each time you press D key you will advance to the next operating parameter To go back you must re enter the installer set up as described above INSTALLER...

Страница 6: ...hould consult with the heating equipment manufacturer for proper use Setting cooling algorithm OP 04 The cooling algorithm can be selected as normal or aggressive For aggressive the system will cool d...

Страница 7: ...and cooling are off Fan Setting Fan switch settings are On Fan symbol is indicated on the display The fan runs continuously Used to improve air circulation and air quality Auto Fan and Auto symbols a...

Страница 8: ...p switch is in the F position the fan is controlled directly by the heating equipment and may start a few minutes after the heating equipment turns on When setup switch is in the E position the fan st...

Отзывы: