6. Protection Functions and Explanations

We make our soft starters have all kinds of protection functions to protect 

the soft starter and the motor using. Please choose the correct protection 

class and parameters according to your application conditions!

Over-heat protection: when the temperature inside soft starter is up to 

80

±5

,the starter will be into over-heat protection, when it down to 

55

,this protection invalid. 

○ 

Input failure-phrase protection: the delayed time

3s 

○ 

Output failure-phrase protection: the delayed time

3s 

○ 

Three-phrase unbalanced protection: the delayed time

3s,when the

 different current value among three phrases is more than 50%±10%,the

 protection be used. 

○ 

Starting over-current protection: the diagram 6.1 shows the protection

 time when the current is 5 

times than the rated working current. 

○ 

Working over-load protection: the starter will be in inverse time thermal 

protection on 

more 

Base of the Max working current of motor (Set by F6 Item),

 (The diagram 6.1 s how) 

○ 

Power voltage failure protection: the delayed time is separately less 

than 0.5s or 3s when the power voltage is less than half of limited value 

or less than setted value. 

○ 

Over-voltage protection: the delayed time is separately less than 0.5s 

or 3s when the power voltage is more than 130% of limited value or more 

than the setted value. 

○ 

Loading short-current protection: when the current is 10 times 

 

than the motor rated current, it will be short circuited, and the short-

current protection will be take effect, the time is less than 0.1s. 

○ 

The time parameters above start from the time receiving the message till 

the protection take effect. The parameters are for reference only, all the protection

function can be proved by the applicaiton or the

 simulated test, 

If it is not meet 

your demand, the special protection is needed to guarantee the safety.

6.2 Protection Classes and Explanations.

According different usage conditions, FWI-SS3 Soft Starter has five 

protection classes, as following: 

a. Primary Protection Level

b. Light-load Protection Level

c. Standard Protection Level

d. Heavy-load Protection Level

e. The Super Protection Level

● 

Primary protection level includes the protection functions of  over-heat,

 short -current protection and input failure-phrase protection when starting,

 but  no  protection of internal connector instantaneous-shop. we can set the 

protection level when the motor don’t need to be stopped urgently, such 

as fire pump. 

more

VTdrive

VTdrive

www.vtdrive.com

www.vtdrive.com

21

22

Содержание FWI-SS3 Series

Страница 1: ...Limited Websie www vtdrive com Email info vtdrive com Tel 86 755 23060667 Headquarters Address 6F Xinfeng Building B Yangguang Industrial Zone Xili Town Nanshan District Shenzhen China Factory Address 3F 4F Xihe Industrial Zone TangTou Load Shiyan Town Baoan District Shenzhen China ...

Страница 2: ...tions for other set items 5 6 Help Message and Explanation 6 Protection Functions and Directions 6 1 Protection Functions and Parameters 6 2 Protection Classes and Explanations 7 Electrical Test and Application 7 1 Electrical Test 7 2 Starting Modes and Application 7 3 Stopping Modes and Application 7 4 Application Examples Safety Precautions Before installation of the soft starter please note the...

Страница 3: ...ions simple and reliable operation every technological is made in the best design Reliable and High grade Quality This product is designed according to the computer analog test has the best electromagnetic compatibility It is proved to behigh quality by the high temperature ageing test and jigging test which done before the products out of factory Complete and Perfect Protection Functions Such as ...

Страница 4: ...s less that 0 5G Note Over more we can manufacture other type soft starters which are used in special conditions such as explosion proof type soft starter low temperature type soft starter or high voltage type soft starter 3 2 The installation Requirement The direction and distance of installation To make suret the soft starter be in good draft and heat dissipation please install the product in ve...

Страница 5: ...3 132 FWI SS3 160 FWI SS3 185 FWI SS3 200 FWI SS3 250 FWI SS3 280 FWI SS3 320 FWI SS3 400 FWI SS3 450 FWI SS3 500 FWI SS3 600 75 90 115 132 160 185 200 250 280 320 400 450 500 600 The FWI SS3 Soft Starter has three types of connection as following Main circuit connection it contains the wiring of 3 phase source input the output to motor and the by pass contactor connection External terminal connec...

Страница 6: ...wo terminals are both open the soft starter will stop and at this time the starter is at the state of fault protection Terminal can be controlled by the output contact of external protection dives and it is useless when the F12Key is set as 0 basic protection Terminal are start up or stop input There two ways of connec tions for your choice those are 3 wire connection and 2 wire connection Please ...

Страница 7: ...ly Stop key is in use And the lamps of ready run and fault are all dark and you can not come into the set and help menu state While in the process of stopping the panel shows XXXX that is the value of start up current At this time only Run key is in use and the lamps of ready run and fault are all dark and you can not come into the set and help menu state The Set key Press Set key to come into the...

Страница 8: ...s code is used to set the voltage value This code is used to set the soft starting 30 70 2 60S 30 16S This code can be used when the starting mode is set as Ramp voltage to start and if is Limit current mode the value will be fixed as 40 It is invalid in Limit Current starting mode time Code Codes Name The range of value Factory Default Explanation P2 P3 P4 P5 P6 This code is used to set the soft ...

Страница 9: ...tage protection 0 Limit current to start 1 Ramp voltage to start 2 Torque control limit current 3 Torque control Ramp voltage 4 Ramp current to start 5 Double closed loop Code Codes Name Setting Range Factory Default Explanation PC PD PE PF PH PJ PL This code is used to adjust protection level 0 4 0 7 0 13 0 2 0 63 0 19 20 100 4 1 0 1 0 7 80 This code is used to set starting time of output of the ...

Страница 10: ...fault If need programmable relay output time delay the delay time is set by P4 code When the PJ is set as 5 9 or 15 19 the programmable operation way is time sequence output As the following form The way of programmable state output is used to show the working state of soft state and under this way the P4 code is invalid The factory default value of PJ code is 7 showing the ready state of soft sta...

Страница 11: ...PD item used to set the control ways of soft starter As the following form Form 5 3 Numerical value keyboard External control Communication 0 1 0 0 1 1 1 0 2 0 1 0 3 0 1 1 4 1 1 1 5 1 0 1 6 0 0 1 7 0 0 0 Note In the above form 1 is allowing 0 is forbidding For e example if you forbid any unexpected stopping or starting whether starting is running or in maintenance you can set the Numerical Value a...

Страница 12: ...an setted value Over voltage protection the delayed time is separately less than 0 5s or 3s when the power voltage is more than 130 of limited value or more than the setted value Loading short current protection when the current is 10 times than the motor rated current it will be short circuited and the short current protection will be take effect the time is less than 0 1s The time parameters abo...

Страница 13: ...efore the If the rated power of soft starter is matched with the Motor or not If the insulation of motor is meet the demand or not If the main circuit connection of input or output is correct or not If all the screws of terminals are twisted tightly or not 7 1 Electrical Test When the power on the soft starter displays the words of CSZPU or READY and the ready lamp is on then press the Run key to ...

Страница 14: ...ter power on or starting if the fault lamp is onand screen displays Err Please check the Form 7 1 to find out the reason according to the error code restoration external stop key Note When the temperature is below 10 the starter should be started after preheated for 30 minute with power on It can back to the to press the stop or the Fault and Solution Form 7 1 Note When the motor starts successful...

Страница 15: ...rce of heavy load then the ramp voltage mode or limit current mode can be used to start the motor Note This mode will cause big current shock to the motor so if the ramp voltage or limit current mode can be used please do not choose to use the torque control mode to start 7 2 4 Ramp Current to start The P9 item is set as 4 this starting mode is valid 7 2 5 Double closed loop Both Ramp Voltage and ...

Страница 16: ...ping This limit current value is a percentage 7 3 2 Free stopping Mode The P2 item is set as 0 this stopping mode is valid When using this mode to stop the motor the Soft Starter will cut off the connection to the by pass contactor and forbid the controlled silicon outputting voltage as soon as receiving the order of stopping The motor stops gradually because of its Inertia Generally if the soft s...

Отзывы: